Cross-Reference Chart; Electrical Ratings - Beckett GeniSys 7505 Specification Sheet

Beckett advanced burner control specification sheet

Advertisement

R.W. Beckett Corporation
Mail: P.O. Box 1289, Elyria, OH 44036 ● Phone: 800-OIL-BURN (800-645-2876) ● FAX: (440)327-1064
R.W. Beckett Canada Ltd.
Unit 3 - 430 Laird Road, Guelph, Ontario, Canada N1G 3X7 ● Phone: 800-665-6972 ● FAX: (519)763-5656
PARTS & ACCESSORIES
www.beckettcorp.com

Cross-Reference Chart

Beckett GeniSys
Lockout
Control Part No.
Time
7505A 0000
15 sec
7505B 1500
15 sec
7505P 1515
15 sec
7505P 1530
15 sec
7505P 152M
15 sec
1) Beckett snap-in alarm module required for direct replacement of the control. 2) Valve-on delay and motor-off delay timings on all models are programmable with Beckett snap-in programming display. Other factory set
timings are available. Contact Beckett for alternate timings.

Electrical Ratings

Inputs
Voltage: 102 to 132 Vac
Current: 150 mA plus burner motor, igniter, and valve loads
Frequency: 60 Hz
Outputs
Motor: 120 Vac, 10 full load amps (FLA*), 60 locked rotor amps (LRA)
Note – Reduce motor FLA rating by igniter current
Igniter: 120 Vac, 3 A @ 0.7 PF min
Solenoid Valve: 120 Vac, 1 A @ 0.7 PF min
Thermostat Anticipator Current: 0.1 A (If applicable)
Thermostat Voltage: 24 Vac (If applicable)
Operation
Sequence of Operation
1
Standby
3
2
Valve-on
Trial for
delay
ignition
5
Ignition
carryover
8
6
Motor-off
Run
delay
Priming The Pump
1.
Initiate a call for heat.
2.
When the burner starts, press and hold the reset button for 15
seconds until the yellow light turns on.
3.
Release the button. The yellow light will turn off and the burner
will start again.
4.
At burner start up, click the reset button while the igniter is still on
to enter Pump Prime mode. The yellow light will turn on.
5.
Bleed the pump until all froth and bubbles are purged.
6.
If necessary, repeat steps 4 and 5 until the pump is fully primed
and the oil is free of bubbles.
7.
When fi nished, hold the reset button or remove the call for heat to
exit Pump Prime mode and return to Standby.
Valve-on
Motor-off
delay time
2
delay time
2
-
-
15 sec
-
15 sec
15 sec
15 sec
30 sec
15 sec
2 min
Application Ratings
Oil Burner Input: < 20gph
Control Programming: UL372 Group 2
Environmental Ratings
Storage & Operating Ambient Temp.: -40°F to +150°F (-40°C to
+65°C)
Moisture: 5 to 95% RH, non-condensing and non-crystallizing
Approvals
Underwriters Laboratory Recognition per UL372 and UL1998,
and CSA C22.2 No. 199
Resetting From Restricted Lockout
If the control locks out three times without a satisfi ed call for
9
Pump
heat or fails the motor relay check, the Lockout becomes
prime
restricted in order to prevent repetitious resetting by the
homeowner. To reset, hold the button down for 15 seconds
4
Lockout
until the red light turns off and the yellow LED turns on.
Disable Function
Any time the burner is running, press and hold the reset
button to disable the burner. The burner will remain off as
7
Recycle
long as the button is held.
Cad Cell Resistance Indicator
During the burner Run state, click the reset button to check
the cad cell fl ame resistance range. The yellow light will fl ash
1 to 4 times depending on the amount of light detected by the
cad cell. See the table below:
Replaces
Honeywell:
R7184A, R8184G
48245, 40200 42230, 50200
R7184B
R7184P, R7184U
1
R7184P, R7184U
1
R7184P, R7184U
1
Yellow LED Flashes
Cad Cell Resistance
1
Normal (0 - 400 ohms)
2
Normal (400 - 800 ohms)
3
Normal (800 - 1600 ohms)
4
Limited (1600 ohms - Lockout)
Form No. 61658 R08, Printed in the USA 04/08