12
en | Specifications
When polled
Maximum allowable line resistance
Maximum airflow
Maximum current consumption isolator base at
77 °F (25 °C) and 39 V bus voltage
Standby
Triggered
Sensitivity
Smoke sensor
Heat sensor (FAP-440 detectors)
Heat sensor (FAH-440 heat detectors)
Installation temperature
Storage temperature
Without CO sensor
With CO sensor
Humidity
Protection category
Mounting locations and heights in general
Maximum spacing between detectors
Smoke detector
Heat detector
Minimum mounting distance to magnets
(e.g. loudspeaker)
Maximum wiring length to C point
Dimensions (diameter x height)
Detector
Detector with 4-inch base
Detector with 6-inch base
Housing material
Table 6.5: Technical Specifications
2018.08 | 6.0 | F.01U.123.589
22 mA ± 20%
50 Ω
4000 ft/min (20m/s)
70 μA
10 mA
1.25%/ft to 3.5%/ft
+135 °F (+57 °C) + RoR
+135 °F to +194 °F (+57 °C to +90 °C), programmable +RoR
+32 °F to +100 °F (0 °C to +38 °C)
If the sensitivity temperature is programmed within a range
of +175 °F to +249 °F (+79.4 °C to +120.6 °C), the maximum
installation temperature is 150 °F (+66 °C).
-13 °F to +176 °F (-25 °C to +80 °C)
+14 °F to +122 °F (-10 °C to +50 °C)
< 95% (non-condensing)
IP 42
Refer to NFPA-72
30 ft.
50 ft.
11.8 in. (30 cm)
9.8 ft. (3 m)
4.4 in. x 2.0 in. (11.2 cm x 5.1 cm)
5.0 in. x 2.5 in. (12.7 cm x 6.4 cm)
7.0 in. x 2.5 in. (17.8 cm x 6.4 cm)
Cycoloy/ABS
Installation Guide
Analog detectors and bases
Bosch Security Systems, Inc.

Hide quick links:

Advertisement