16 Outdoor Unit Installation

5.1.2. Unit mounting dimensions

The following is a list of different outdoor model sizes and the distance
between their mounting feet. Prepare the installation base of the unit
according to the dimensions below.
Air inlet
Air outlet
Outdoor Unit
Dimensions (mm/in)
WxHxD
681x434x285
(26.8"x17"x11.2")
700x550x270
(27.5"x21.6"x10.62")
780x540x250
(30.7"x21.25"x9.85")
845x700x320
(33.25"x27.5"x12.6")
810x558x310
(31.9"x22"x12.2")
700x550x275
(27.5"x21.6"x10.82")
770x555x300
(30.3"x21.85"x11.81")
800x554x333
(31.5"x21.8"x13.1")
845x702x363
(33.25"x27.63"x14.29")
900x860x315
(35.4"x33.85"x12.4")
945x810x395
(37.2"x31.9"x15.55")
Bosch Climate 5000
Air inlet
Figure 5-5
Mounting Dimensions
Distance A
Distance B
(mm/in)
(mm/in)
460 (18.10")
292 (11.49")
450 (17.7")
260 (10.24")
549 (21.6")
276 (10.85")
560 (22")
335 (13.2")
549 (21.6")
325 (12.8")
450 (17.7")
260 (10.24")
487 (19.2")
298 (11.73")
514 (20.24")
340 (13.39")
540 (21.26")
350 (13.8")
590 (23.2")
333 (13.1")
640 (25.2")
405 (15.95")
Outdoor Unit
Dimensions (mm/in)
WxHxD
946x810x420
(37.21 "x31.9"x16.53")
946x810x410
(37.21"x31.9"x16.14")
If you install the unit on the ground or on a concrete mounting platform,
the following is required:
1
Mark the positions for four expansion bolts based on the dimensions
in the Unit Mounting Dimensions chart.
2
Pre-drill holes for expansion bolts.
3
Clean concrete dust away from holes.
4
Place a nut on the end of each expansion bolt.
5
Hammer expansion bolts into the pre-drilled holes.
6
Remove the nuts from expansion bolts, and place outdoor unit on
bolts.
7
Put washer on each expansion bolt, then replace the nuts.
8
Using a wrench, tighten each nut until tight.
WHEN DRILLING INTO CONCRETE, EYE AND EAR PROTECTION IS
RECOMMENDED AT ALL TIMES.
If you will install the unit on a wall-mounted bracket, we recommend
following:
Before installing a wall-mounted unit, make sure that the wall is load
bearing for the weight of the unit and made of solid brick, concrete, or of
similarly strong material. The wall must be able to support at least four
times the weight of the unit.
1
Mark the position of bracket holes based on dimensions in the Unit
Mounting Dimensions chart.
2
Pre-drill the holes for the expansion bolts.
3
Clean dust and debris away from holes.
4
Place a washer and nut on the end of each expansion bolt.
5
Thread expansion bolts through holes in mounting brackets, put
mounting brackets in position, and hammer expansion bolts into the
wall.
6
Check that the mounting brackets are level.
7
Carefully lift unit and place its mounting feet on brackets.
8
Bolt the unit firmly to the brackets.
Mounting Dimensions
Distance A
Distance B
(mm/in)
(mm/in)
673 (26.5")
403 (15.87")
673 (26.5")
403 (15.87")
WARNING
CAUTION
6 720 866 139 (2016/07)