Download Print this page

Toshiba 4400 Series Installation Instructions Manual page 5

Ups seismic adapter kit

Advertisement

2. 4400 50kVA Seismic Installation
Table 2 lists the contents of the 4400 50kVA (4400500SEISMICKIT) and 80kVA (4400800SEISMICKIT)
Seismic Kits. Figure 1 shows the order of assembly for the [bolt + lockwasher + washer] fastener group.
TABLE 2 50 KVA SEISMIC KIT CONTENTS
440500SEISMICKIT Contents
No.
P/N*
5
66437
TOP SEISMIC BRACKET
6
67193
SEISMIC MOUNTING CHANNEL
7-a
Hex Bolt, 1/4—20,1-1/2"
7-b
Flat Washer, 1/4
7-c
E—Ring, F/0.25 Shaft
10-a
Hex Bolt, 1/2—13 x 3/4"
10-b
Lock Washer, 1/2
10-c
Flat Washer, 1/2
11-a
Hex Bolt, 5/16—18 x 1"
11-b
Lock Washer, 5/16
11-c
Flat Washer, 5/16
94016
4400 Seismic Kit Installation Manual
1. Prepare the floor anchorages. Arrange the anchorages to ac-
commodate the final layout including placement for ancillary
battery and/or Auxiliary cabinets. (Figure 11)
2. Prepare the wall anchorages. Key measurements off the an-
chorage placement in Step 1. (Figure 12)
3. Table 2 lists the components of the 50kVA Seismic Kit. Figure 10
show the Seismic anchorage components in the Seismic Kit for
the 50kVA cabinets.
4. Assemble the fastener groups in Table 2, [7a-7c], [10a-10c], and
[11a-11c] as shown in Figure 1.
5. Secure the Top Seismic Bracket [5] to the top rear of the UPS
using three (3) fastener group [11].
6. Position the UPS over the floor anchors
7. Slip each Seismic Mounting Channel [6] over the three floor
anchors on each side of the UPS.
8. Tilt the Base bracket up against the UPS bottom bracket on the
UPS base.
9. Align the holes in the Seismic Mounting Channels [6] with the
UPS bottom brackets.
10. Use the remaining eight (8) fastener group [11] to secure the
Seismic Mounting Channels [6] to the UPS bottom brackets.
(Figure 14, Figure 15)
11. Secure the Top Seismic Bracket to the wall anchors using 5/16" Bolts.
12. Once installation is complete, secure the door of the UPS using the two
(2) Fastener Group [7].
4400 Series UPS Seismic Kit Installation Instructions – 94016-001
Description
(Figure 13)
(Figure 16)
Quan
1
a
2
1
b
1
c
1
FIGURE 1: FASTENER
8
GROUP (BOLT +LOCK
WASHER + WASHER)
8
8
4
4
4
1
7
P/N 440500SEISMICKIT
FIGURE 10: SEISMIC KIT
COMPONENTS (50 KVA)
5
5
6
5