Sanyo PW-UMR184EXH56 Installation And Operation Manual
Sanyo PW-UMR184EXH56 Installation And Operation Manual

Sanyo PW-UMR184EXH56 Installation And Operation Manual

Eco-i system air conditioner

Advertisement

R410A Models
I
Indoor Units
SPW-UMR74EXH56
SPW-UMR94EXH56
SPW-UMR124EXH56
SPW-UMR164EXH56
SPW-UMR184EXH56
SPW-UMR224EXH56
Outdoor Units
DC Inverter Main Unit
C
Constant Speed (Sub) Unit
* Refrigerant R410A is used in the outdoor units.
Optional Controllers
Remote Controller
RC Wireless Remote Controller
Simplified Remote Controller
37.4196.054.0 ©SANYO 2005
INSTALLATION AND OPERATION MANUAL
– ECO-i System Air Conditioner –
for Refrigerant R410A
SPW-CR604GDXH8, SPW-CR704GDXH8, SPW-CR904GDXH8, SPW-CR1154GDXH8
SPW-CR704GDCH8, SPW-CR904GDCH8, SPW-CR1154GDCH8
RCS-SH80AG
RCS-BH80AG.WL
RCS-KR1AG
SANYO Airconditioners Europe S.r.l.
Via Bisceglie, No. 76
20152 Milano, Italy

Advertisement

Table of Contents
loading

Summary of Contents for Sanyo PW-UMR184EXH56

  • Page 1 * Refrigerant R410A is used in the outdoor units. Optional Controllers Remote Controller RC Wireless Remote Controller Simplified Remote Controller 37.4196.054.0 ©SANYO 2005 for Refrigerant R410A RCS-SH80AG RCS-BH80AG.WL RCS-KR1AG SANYO Airconditioners Europe S.r.l. Via Bisceglie, No. 76 20152 Milano, Italy...
  • Page 2: Important

    Be careful when picking up and moving the indoor and outdoor units. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges or thin aluminum fins on the air conditioner can cut your fingers. When Installing… …In a Room Properly insulate any tubing run inside a room to prevent “sweating”...
  • Page 3: Check Of Density Limit

    If a single unit of the multi air conditioner system is to be installed in a small room, select a suitable model and installation procedure so that if the refrigerant acci-...
  • Page 4: Table Of Contents

    IMPORTANT ......2 Please Read Before Starting Check of Density Limit 1.
  • Page 5: How To Install The Unit

    2. HOW TO INSTALL THE UNIT Minimum operation and maintenance area. (fig. 2-1) Find the space for the installation of the return air grille and mark the opening to do. Cut the falseceiling. (fig. 2-2) Use rawl plug suitable to the ceiling consistence and four M10 threaded bars of suitable length (not supplied).
  • Page 6: Duct For Fresh Air

    On the front and rear side of the unit a rectangular port Outlet conduct (with flange) helps during duct mounting. (fig. 2-10) Rear and front flange for the air intake. The value included Intake coduct in the brackets is referred to the model X18. (fig. 2-11) Discarge air duct (optional accessory).
  • Page 7: Test Of The System And Control Of The Air Volume To The Outlet Grilles

    3. TEST OF THE SYSTEM AND CONTROL OF THE AIR VOLUME TO THE OUTLET GRILLES The unit is prearranged to supply an external static pressure of about 5 mm. Too high resistances in the air distribution system can cause an exceedingly small air volume to the outlet grilles.
  • Page 8: Electrical Wiring

    Max. 1,000 m NOTE * With ring-type wire terminal. (7) Regulations on wire diameters differ from locality (8) To prevent malfunction of the air conditioner (9) If the power supply cord of this appliance is dam- Time delay fuse or circuit capacity...
  • Page 9: Wiring System Diagrams

    4-3. Wiring System Diagrams Indoor unit (No. 1) Power supply 220-240V 50Hz Ground Remote controller Indoor unit (No. 2) Power supply 220-240V 50Hz Ground Remote controller Indoor Group control: unit (No. 3) Power supply 220-240V 50Hz Ground Indoor unit (No. n) Power supply 220-240V 50Hz...
  • Page 10 CAUTION (1) When linking outdoor units in a network (S-net link system), disconnect the terminal extended from the short plug (CN003, 2P Black, location: right bottom on the outdoor main control PCB) from all outdoor units except any one of the outdoor units. (When shipping: In shorted condition.) Otherwise the communication of S-net link system is not performed.
  • Page 11 (5) Use shielded wires for inter-unit control wiring (c) and ground the shield on both sides, other- wise misoperation from noise may occur. (Fig. 4-4) Connect wiring as shown in Section “4-3. Wiring System Diagrams.” Loose wiring may cause the terminal to overheat or WARNING result in unit malfunction.
  • Page 12: How To Process Tubing

    5. HOW TO PROCESS TUBING The narrow tubing side is connected by a flare nut, and the wide tubing side is connected by brazing. 5-1. Connecting the Refrigerant Tubing Use of the Flaring Method Many of conventional split system air conditioners employ the flaring method to connect refrigerant tubes which run between indoor and outdoor units.
  • Page 13: Connecting Tubing Between Indoor And Out- Door Units

    Caution Before Connecting Tubes Tightly (1) Apply a sealing cap or water-proof tape to prevent dust or water from entering the tubes before they are used. (2) Be sure to apply refrigerant lubricant to the match- ing surfaces of the flare and union before connect- ing them together.
  • Page 14: Insulating The Refrigerant Tubing

    5-3. Insulating the Refrigerant Tubing Tubing Insulation Thermal insulation must be applied to all unit tub- ing, including distribution joint (purchased sepa- rately). * For gas tubing, the insulation material must be heat resistant to 120°C or above. For other tubing, it must be heat resistant to 80°C or above.
  • Page 15: Taping The Tubes

    5-4. Taping the Tubes (1) At this time, the refrigerant tubes (and electrical wiring if local codes permit) should be taped together with armoring tape in 1 bundle. To pre- vent the condensation from overflowing the drain pan, keep the drain hose separate from the refrigerant tubing.
  • Page 16: Appendix

    Air outlet Water drain I Care and Cleaning 1. For safety, be sure to turn the air conditioner off and also to disconnect the power before WARNING cleaning. 2. Do not pour water on the indoor unit to clean it. This will damage the internal compo- nents and cause an electric shock hazard.
  • Page 17: Troubleshooting

    Care: After a prolonged idle period Care: Before a prolonged idle period I Troubleshooting If your air conditioner does not work properly, first check the following points before requesting service. If it still does not work properly, contact your dealer or a service center. Trouble 1.
  • Page 18: Entretien Et Nettoyage

    I Nom des pièces (unité intérieure) Sortie d í a ir I Entretien et nettoyage 1. Pour toute sécurité, éteignez le climatiseur et débranchez-le de la prise secteur. AVERTISSEMENT 2. Ne versez pas d’eau sur l’unité intérieure pour la nettoyer. Cela pourrait abîmer les com- posants internes et provoquer des décharges électriques.
  • Page 19 1. Certains bords métalliques et les ailettes du condensateur étant coupants, ils doivent être manipulés avec précaution lors du nettoyage sous peine de provoquer des blessures. ATTENTION 2. Vérifiez régulièrement que la sortie et l’arrivée d’air ne soient pas obstruées par de la poussière ou de la suie.
  • Page 20 I Guide de dépannage Si le climatiseur ne fonctionne pas correctement, effectuez les vérifications suivantes avant de faire appel à un réparateur. Si le problème persiste, prenez contact avec votre concessionnaire ou avec un service après-vente. Panne Le climatiseur ne fonctionne pas du tout.
  • Page 21: Pflege Und Reinigung

    I Bezeichnungen der Teile Luftauslass Wasserablass I Care and Cleaning I Pflege und Reinigung 1. Aus Sicherheitsgründen darauf achten, das Gerät vor dem Reinigen auszuschalten und es außerdem vom Netz zu trennen. WARNUNG 2. Kein Wasser auf die Inneneinheit schütten, um diese zu reinigen. Dadurch werden die inneren Bauteile beschädigt, und es besteht Stromschlaggefahr.
  • Page 22 1. Gewisse Metallkanten und die Kondensatorrippen sind scharf und können Verletzungen VORSICHT verursachen, wenn Sie nicht richtig gehandhabt werden. Seien Sie daher beim Reinigen dieser Teile besonders vorsichtig. 2. Überprüfen Sie die Außeneinheit regelmäßig, um zu sehen, ob Luftauslass oder Luftein- lass mit Staub oder Ruß...
  • Page 23 I Fehlersuche Wenn Ihr Klimagerät nicht richtig funktioniert, zuerst die folgenden Punkte überprüfen, bevor ein Kundendiensttechniker ange- fordert wird. Läßt sich die Störung nicht beheben, so wenden Sie sich bitte an Ihren Fachhändler oder an eine Kundendienst- stelle. Störung Das Klimagerät läuft überhaupt 1.
  • Page 24 I Nome delle parti (Unità interna) Uscita d’aria Scarico dell’acqua I Cura e manutenzione 1. Per motivi di sicurezza, accertare che il condizionatore d’aria sia spento e che la spina AVVERTIMENTO del cavo di alimentazione sia staccata dalla presa di corrente prima di procedere con le operazioni di pulizia.
  • Page 25 1. Alcuni bordi metallici e le alette del condensatore sono taglienti e possono causare ferite se maneggiati in modo incorretto; occorre pertanto prestare particolare attenzione nel PRECAUZIONE pulire tali componenti. 2. Controllare periodicamente l’unità esterna, accertando che l’uscita d’aria e la presa d’aria non siano ostruite da sporco o fuliggine.
  • Page 26 I Prima di chiamare il tecnico Se il condizionatore d’aria non funziona correttamente, prima di chiamare il tecnico per la riparazione controllare quanto segue. Se ciò non consente di eliminare il problema, rivolgersi al proprio rivenditore o centro di assistenza. Problema Il condizionatore d’aria non 1.
  • Page 27: Cuidados E Limpeza

    I Nomenclatura das peças (unidade interior) Saída de ar Drenagem de água I Cuidados e limpeza 1. Por motivos de segurança desligue o aparelho de ar condicionado e desligue-o também ADVERTÊNCIA da rede antes de proceder à sua limpeza. 2. Não verta água sobre a unidade interior para a limpar. Poderá danificar os componentes internos e causar descargas eléctricas.
  • Page 28 1. Algumas bordas metálicas e as pás do condensador são pontiagudas e podem causar ferimentos se não forem manuseadas com cuidado; tenha especial cuidado ao limpar PRECAUÇÃO estas peças. 2. Inspeccione periodicamente a unidade exterior para verificar se a entrada ou a saída de ar estão bloqueadas com sujidade ou fuligem.
  • Page 29 I Resolução de problemas Se o seu aparelho de ar condicionado não funciona correctamente, verifique primeiro os seguintes pontos antes de solicitar assistência. Se não conseguir solucionar o problema, contacte o seu concessionário ou o serviço de assistência. Avaria O aparelho de ar condicionado não funciona de maneira nenhuma.
  • Page 30 Air outlet Water drain Air filter...
  • Page 33: Cuidados Y Limpieza

    I Nombres de las partes (unidad interior) Salida de aire Drenaje de agua I Cuidados y limpieza 1. Por motivos de seguridad, asegúrese de apagar el acondicionador de aire, y desconec- tarlo también de la red eléctrica antes de realizar su limpieza. ADVERTENCIA 2.
  • Page 34 1. Algunos bordes metálicos y las aletas del condensador son agudos y podrán ocasionar heridas si se manejan incorrectamente; cuando limpie estas partes deberá tener cuidado PRECAUCIÓN especial. 2. Compruebe periódicamente la unidad exterior para ver si la salida de aire o enterada de aire está...
  • Page 35 I Localización de averías Si su acondicionador de aire no funciona correctamente, compruebe primero la lista de abajo antes de llamar al servicio de reparaciones. Si no puede solucionar el problema, póngase en contacto con su concesionario o centro de reparaciones. Avería El acondicionador de aire no funciona en absoluto.