35. Connect Switchgear B+ and Battery Module #17 B+ using ―BUSBAR_BUSBAR M TO SG.‖ Switchgear B+ terminal
is connected using an M12 screw and Module #17 B+ terminal is connected using an M8 screw.
Figure 3-70: Connect Switchgear B+ and Module #17 B+.
36. Reattach Battery Module #17's front cover and Switchgear B+ terminal cover.
Figure 3-71: Reattach Battery Module #16's Front Cover and Switchgear B+ Terminal Cover