Checking VxWorks image file

Check that VxWorks image files of the personal computer and C intelligent function module are in the same version before
debugging the user program.
The image files of different version cannot debug normally.
(2)
(1)
(1) VxWorks image file
(2) Same version
Checking method
The checking methods for the VxWorks image file are shown below.
■C intelligent function module
Check the firmware version with the diagnostic function of an engineering tool or the rating plate on the C intelligent function
module side.
■Personal computer
Check the file name of VxWorks image file specified with CW Workbench.
*1
• RD55UP06-V_XX
*1 XX: Firmware version
If the version is different
If the version of VxWorks image file is different, acquire the new image file stored in the C intelligent function module.
1.
Connect a C intelligent function module with a personal computer. ( Page 36 WIRING)
2.
Acquire the VxWorks image file
*1 Stored in the system memory (/SYSTEMROM/OS_IMAGEFILE).
3.
Reconfigure the target server setting with CW Workbench.
The default settings of the FTP function are as follows:
• Login name: target
• Password: password
4 PROCEDURE BEFORE OPERATION
28
4.2 Creating User Program
(1)
*1
using FTP function from the C intelligent function module.