Safety Information

Only trained and qualified personnel should be allowed to install, replace, or service this equipment.
Caution
Statement 1030
Warning
Connect the unit only to DC power source that complies with the safety extra-low voltage (SELV)
requirements in IEC 60950 based safety standards.
Warning
When installing or replacing the unit, the ground connection must always be made first and
disconnected last.
Do not locate the antenna near overhead power lines or other electric light or power circuits, or
Warning
where it can come into contact with such circuits. When installing the antenna, take extreme care
not to come into contact with such circuits, because they may cause serious injury or death. For
proper installation and grounding of the antenna, please refer to national and local codes (for
example, U.S.:NFPA 70, National Electrical Code, Article 810, Canada: Canadian Electrical Code,
Section 54).
Installation of the equipment must comply with local and national electrical codes. Statement 1074
Warning
The BS must be installed in accordance with NEC/CEC Articles 800/810/830.
1.
At a minimum, all DC power leads and bonding/grounding straps shall be 6 AWG or 8 AWG copper
2.
conductors.
Power cables in excess of 140 feet in length must have protective devices installed that are UL listed
3.
to UL 492, UL497A or UL497B, UL497C, and UL1449.
The BS must be connected to a power supply/rectifier that is IEC 60950-1 certified (UL listed to
4.
UL60950-1 in North America) having a SELV output.
5.
All power and ground conductors must be mechanically supported to avoid strain of the wires and
connection points.
6.
There must not be a switch or disconnect device installed in the ground cabling.
A UL listed disconnect device, such as a circuit breaker, must be installed between the power supply
7.
and BS chassis connections. The BWX 8415 BS requires a 60V, 15A, 1 sec. max break time circuit
breaker.
Power-interconnect wires between the power supply/rectifier and the BS unit must have heat shrink
8.
tubing applied over the barrel of the terminal lugs after crimping the wire. A picture is provided in
the "Installation" section of this manual.
External power source / supply considerations for the - 40.5V DC to - 58.0V DC BS chassis:
9.
a.
b.
BWX 8415 Basestation Installation and Commissioning Guide
1-4
P R E L I M I N A R Y
Statement 1046
Statement 1052
An external method of disconnecting each of the DC power Load/Return lines to the BS chassis
is required (i.e. - fuse + disconnect device). The BWX 8415 BS requires a 15A circuit breaker.
The external power supply shall be at least 1000 Watt rating, with a maximum current > 20