Digital switches

Advertisement

Quick Links

WARNINGS AND CAUTIONS:
• TO BE INSTALLED AND/OR USED IN ACCORDANCE WITH APPROPRIATE ELECTRICAL CODES AND REGULATIONS.
• IF YOU ARE NOT SURE ABOUT ANY PART OF THESE INSTRUCTIONS, CONSULT AN ELECTRICIAN.
• DO NOT CONNECT LINE VOLTAGE WIRES TO LOW VOLTAGE TERMINALS.
• FOR THE BEST LAMP LIFE, LAMP MANUFACTURERS RECOMMEND THEIR FLUORESCENT LAMPS SHOULD BE OPERATED AT FULL BRIGHTNESS FOR A MINIMUM
OF 100 HOURS BEFORE DIMMING IS PERMITTED. FOR BEST RESULTS, LAMP BRANDS AND TYPES SHOULD NOT BE INTERMIXED ON A CIRCUIT.
• DISCONNECT POWER WHEN SERVICING THE DIMMER, FIXTURE OR WHEN CHANGING LAMPS.
• FOR INDOOR USE ONLY.
• TO AVOID FIRE, SHOCK OR DEATH: TURN OFF POWER AT MAIN CIRCUIT BREAKER OR FUSE AND TEST THAT THE POWER IS OFF BEFORE WIRING!
INTRODUCTION:
For best results using the Z-MAX
TM
1. Plan the system before beginning the installation
2. Terminate the wiring
3. Test the wiring
4. Connect relay cabinets
5. Check voltages
NOTE: If the lighting control fails or becomes sporadic, first check the wiring or network ID.
MINIMUM BACK BOX DIMENSIONS:
• NEMA (US) markets:
1 gang device back box, 1-1/2" deep.
• For IEC (3x3) markets: 1 gang device back box, min 35mm deep, 47mm preferred.
Minimum vertical clearance 69mm, minimum horizontal clearance 45mm.
Designed for horizontal screw mounting.
TERMINATING THE WIRING:
Luma-Net
®
III
Control Stations can be located up to 2000 ft. from the dimming cabinet. Luma-Net
configuration is desired, a Hub can be used. The cable should not pass near any source of electrical noise such as fluorescent circuits or motor wiring. Avoid close proximity to any
AC wiring. All control/power wiring must be in conduit.
Luma-Net
Wire Recommendations
®
Leviton strongly recommends the use of Belden 1502R or 1502P for Luma-Net
specifications above, may also be used. Standard voltage drop for DC power systems can be used. Stations require a minimum of +10VDC in order to be effective.
1. Use RS485 compatible cable for communications. It is recommended that a cable with 2 Twisted Pair, 24 AWG (min.), stranded conductors be used. The spare pair is for future uses.
2. Capacitance of wire shall be 15pF/ft. or less.
3. Normal Impedance of wire shall be between 100-120 ohms.
4. Drain/Shields to be tied together, insulated and grounded at one point only.
5. A second pair of stranded wire is required for the power.
CONTROL
STATION
ENTRY
STATION
NOTE: Dimmer or Realy cabinet can be in the middle of a daisy chain
NOTE: All control wiring is Class 2.
If a remote DC power supply is used and you have multiple Luma-Net
At the last control station or dimmer cabinet on both ends of run, a small jumper wire must be run from the terminal labeled "Rem-" to the terminal marked "Term" on that last station.
This jumper wire properly terminates the digital communications lines at both ends of the line.
Power Consumption
• Input Power: 24 VDC
• Consumption:
Station
Unit Load Consumption @ 24 VDC
1 Unit Load = 25mA
1 button
0.6
2 button
0.8
3 button
1.0
4 button
1.1
5 button
1.3
6 button
1.0
8 button
1.1
10 button
1.3
Z-MAX
Digital Switches, follow these recommendations:
6. Power up the stations
7. Program each station
8. Install all stations
LUMA-NET
Dimmer or
Relay Cabinet
Equipped
with
Luma-Net
®
®
Wire the Phoenix/ Luma-Net
1. Connect leads per wiring diagram (see Luma-Net
Wire Connections).
2. Twist strands of each lead tightly (making sure that
there are no stray strands) and push firmly into
appropriate plug connector location.
3. Tighten the screws on the plug connector-making
sure that no bare conductor is showing.
4. Tie the Drain/Shield wires together and insulate
using a small piece of heat shrink tubing.
5. Install termination jumpers as required. Remember
a termination jumper is required at the two ends of
the Luma-Net
Digital Switches
TM
Assign unique network ID numbers to stations.
Check the proper operation of each station as it is installed when multiple stations are involved.
is wired Daisy Chained, station to station. For applications where runs become too long, or a star
®
®
wire runs. Other Belden cables, ex: #9829 & 9729, or RS-485 cable compliant with the
CONTROL
STATION
HUB
®
ENTRY
STATION
Dimmer or
Relay Cabinet
Equipped
with
Luma-Net
runs, all DC common wires must be joined at the power supply.
Connector
®
run.
®
ENTRY
ENT
STATION
STATIO
®
Drain/Shield - Insulated & tied together
(Ground at one point only - probably an end)
®
Install termination
jumper if last station on
Luma-Net
Wire Connections for runs
®
longer than 1,000 ft.
DI-000-ZMDSW-00D
CONTROL
CONTROL
STATION
Dimmer or
Re
Relay Cabinet
Equipped
Equip
with
h
Luma-Net
Net
®
2 #12AWG
Black (Common)
2 #12AWG
Red (+V)
Phoenix/Luma-Net
Connector
®

Advertisement

loading
Need help?

Need help?

Do you have a question about the Z-MAX ZMDSW-S1W and is the answer not in the manual?

Questions and answers

Summary of Contents for Leviton Z-MAX ZMDSW-S1W

  • Page 1 Luma-Net Wire Recommendations ® Leviton strongly recommends the use of Belden 1502R or 1502P for Luma-Net ® wire runs. Other Belden cables, ex: #9829 & 9729, or RS-485 cable compliant with the specifications above, may also be used. Standard voltage drop for DC power systems can be used. Stations require a minimum of +10VDC in order to be effective.
  • Page 2 Leviton’s only obligation is to correct such defects by repair or replacement, at its option, if within such two year period the product is returned prepaid, with proof of purchase date, and a description of the problem...

This manual is also suitable for:

Z-max zmdsw-s2wZ-max zmdsw-s3wZ-max zmdsw-s5wZ-max zmdsw-s4w