Mk2000 series

Advertisement

Quick Links

This document is intended as a reference guide to installing and setting a MK2000 series remote in-
dicator. This document includes installation instructions and typical front plate display indications of
the device. For complete details, including installation, setup, settings, and troubleshooting, refer to
document NAE2025010, "LIM2010 User Manual. "
Only qualified maintenance personnel shall operate or service this equipment. These instructions
should not be viewed as sufficient for those who are not otherwise qualified to operate or service
this equipment. This document is intended to provide accurate information only. No responsibility
is assumed by BENDER for any consequences arising from use of this document. This device series is
intended for use only with the BENDER LIM2010 Line Isolation Monitor.
Applicable Devices
This document applies to the following remote indicators:
MK2000 ( - G1 / G2)
MK2000P (- G1 / G2)
MK2000C (- G1 / G2)
MK2000CP ( - G1 / G2)
For MK2000CBM remote indicators, refer to document NAE2028450 for installation instruc-
tions. For all other remote types, refer to the respective user manual for installation instruc-
tions.
Installation
Mounting
Single-gang plates provide two holes at the top and bottom for screw mounting. Two-gang
plates provide four holes (Two at the top, two at the bottom) for screw mounting. Use the pro-
vided screws for mounting. MK2000 series remotes utilize standard size gang plates. Refer to
Figure 1 for single-gang plates, and Figure 2 for two-gang plates.
2.8" (71.1)
Figure 1 - Single-gang wall plate dimensions in inches (mm)
Figure 2 - Two-gang wall plate dimensions in inches (mm)
Bender Inc. • USA: 800.356.4266 / 610.383.9200 / medical@bender.org • Canada: 800.243.2438 / 905.602.9990 / info@bender-ca.com • www.bender.org
T M
Mute
Mute, test
Mute, overload
Mute, test, overload
1.6" (40.6)
4.6" (116.8)
MK2000(C)(P) Series
Installation Bulletin / Reference Guide
Wiring
MK2000 series remotes connect to a connector plate as-
sembly, which is connected to the LIM2010 Line Isola-
tion Monitor. Ensure that the LIM2010 and correspond-
ing connector plate have already been installed.
Locate the wiring diagram for the correct MK2000
series remote on the reverse side of this document.
For more information on the connector plate and in-
stallation, refer to the LIM2010 User Manual, document
NAE2025010.
Wiring - Remote Muting
Remote indicators that do not have bus capability may be muted collectively by connecting
terminals 7 and 8 on the remote to terminal RI2 on the LIM2010. No matter how the wiring
is configured, each respective device is able to mute itself. Wiring between the remote and
the LIM2010 will affect whether a particular device will mute more than itself. Refer to Table
1 below for details.
Table 1 - Terminal connections for remote muting
MK2000(C)(P)
LIM2010
Terminal
Terminal 7
Terminal 8
RI2
--
--
--
X
X
--
X
--
X
X
X
X
Front Panel Display (Example: MK2000CP-G1)
NOTE: Depending on the type of remote, not all features shown in the image below may be
available. Consult the list below or the manufacturer for more details.
1
2
3
Figure 3 - MK2000CP-G1 diagram
1.
Green "SAFE" LED. Illuminates when the
connected LIM2010 is in the normal
condition.
2.
Amber "OVERLOAD" LED (Only avail-
able with MK2000C and MK2000CP).
Illuminates when the connected
LIM2010's transformer overload alarm is
active.
3.
Red "HAZARD" LED. Illuminates when
the connected LIM2010 is in the alarm
condition.
! DANGER
HAZARD OF ELECTRIC SHOCK,
EXPLOSION, OR ARC FLASH
• Disconnect all power before servicing.
• Reference NFPA 99 / CSA Z32 for
Installation Standard.
Effect
Only the local device will be muted.
The LIM2010 mute button will mute both devices.
The MK2000 mute button will mute both devices.
Both mute buttons will mute both devices.
4
5
4.
TEST button (Only available with
MK2000P and MK2000CP). Initiates a
self-test of the connected LIM2010.
5.
MUTE button with amber LED. Mutes
the audible alarm when in the alarm
condition. The amber LED indicates that
the audible alarm has been muted.
Document NAE2028520 • 08.2015 • © Bender Inc. • Page 1/1 • Side 1/2

Advertisement

loading

Summary of Contents for Bender MK2000

  • Page 1 MK2000(C)(P) Series Installation Bulletin / Reference Guide This document is intended as a reference guide to installing and setting a MK2000 series remote in- dicator. This document includes installation instructions and typical front plate display indications of the device. For complete details, including installation, setup, settings, and troubleshooting, refer to document NAE2025010, “LIM2010 User Manual.