Download Print this page
GE GTP0060U0101 Installation Instructions

GE GTP0060U0101 Installation Instructions

Entelliguard tu rating plugs, for power break, power break ii, akr, wavepro, entelliguard g/microentelliguard circuit breakers and trip unit conversion kits

Advertisement

Quick Links

GE Energy
Industrial Solutions
DEH-41318 Installation Instructions
EntelliGuard
For Power Break
®
EntelliGuard
G / microEntelliGuard
®
Function
EntelliGuard TU Trip Units are designed with UL-Listed
interchangeable rating plugs. These rating plugs
change the per-unit (1X) continuous current rating of
the breaker. A circuit breaker frame equipped with a
suitable rating plug has a long-time trip value equal
to the ampere rating marked on the rating plug. For
example, a breaker frame with a 1600 A sensor and
an 800 A rating plug has an 800 A continuous current
(long-time) rating.
The available rating plugs for the AKR , Power Break,
WavePro and EntelliGuard families are listed in Table 1.
Not all sensors listed in Table 2 are available in all circuit
breakers.
Table 1. Rating plug catalog numbers
GTP0060U0101
GTP0080U0101
GTP0100U0103
GTP0125U0103
GTP0150U0104
GTP0200U0204
GTP0225U0306
GTP0250U0407
GTP0300U0408
GTP0350U0408
GTP0400U0410
GTP0450U0612
GTP0500U0613
GTP0600U0616
GTP0700U0816
GTP0750U0820
GTP0800U0820
GTP0900U1020
GTP1000U1025
* For use with ITE 4000A conversion kits ONLY
®
, Power Break
II, AKR, WavePro
®
GTP1100U1225
GTP1200U1232
GTP1500U1640
GTP1600U1640
GTP1900U2050
GTP2000U2050
GTP2200U2550
GTP2400U2564
GTP2500U2564
GTP3000U3064
GTP3200U3264
GTP3600U4064
GTP4000U4064
GTP5000U5064
GTP6000U6064
GTP1600K4040*
GTP2000K4040*
GTP3000K4040*
GTP4000K4040*
TU Rating Plugs
,
®
Circuit Breakers and Trip Unit Conversion Kits
TM
Front Label
Figure 1. Front of rating plug, showing label
The front label, shown in Figure 1, is visible when the
rating plug is installed. The items listed are:
Rating Plug Amps (X) The rating plug continuous
Catalog Number
In this example:
GTP = EntelliGuard TU trip unit rating plug
1100 = The rating plug continuous current in amperes
U = Universal Trip Plug (Use K for ITE 400A sensor
conversion kit)
12 = Smallest sensor that accepts this plug (1200A)
25 = Largest sensor that accepts this plug (2500A)
Table 2. Catalog number sensor rating designations
Sensor Designation
01
02
03
04
06
07
08
10
12
13
16
20
25
30
32
40
50
60
64
current in amperes
GTP1100U1225
Sensor Rating
150A
200A
225A
400A
600A
630A
800A
1000A
1200A
1250A
1600A
2000A
2500A
3000A
3200A
4000A
5000A
6000A
6400A

Advertisement

loading

Summary of Contents for GE GTP0060U0101

  • Page 1 GE Energy Industrial Solutions DEH-41318 Installation Instructions EntelliGuard TU Rating Plugs ® For Power Break , Power Break II, AKR, WavePro ® ® ® EntelliGuard G / microEntelliGuard Circuit Breakers and Trip Unit Conversion Kits ® Function Front Label EntelliGuard TU Trip Units are designed with UL-Listed interchangeable rating plugs.
  • Page 2 Should further information be desired or should particular problems arise that are not covered sufficiently for the purchaser’s purposes, the matter should be referred to the GE Company. GE Energy 41 Woodford Avenue, Plainville, CT 06062 www.geelectrical.com...

This manual is also suitable for:

Gtp1100u1225Gtp0080u0101Gtp1200u1232Gtp0100u0103Gtp1500u1640Gtp0125u0103 ... Show all