• Electric heat is removable from the side� Means easier system with minimal room modifications. access if required� The VertiCool Space Saver has been engineered for use in • Water service connections are flush with the side of the free blow plenum applications or ducted applications� The cabinet�...
Engineering Guide Space Saver VertiCool Space Saver’ Product Features The VertiCool “Space Saver” Series of units are small Partial List of Options (Items in BOLD are factory installed): footprint units� They are available as water cooled, air cooled (remote condenser or condensing section required), •...
Engineering Guide Space Saver Air-Cooled Performance Data Air Over Condenser Entering Air Temp. Deg. F Tons Total Sensible Total Sensible Total Sensible 26673 19212 24209 18202 21648 17112 62.5 24699 18849 22297 17740 19938 16767 23671 18522 21358 17495 19006 16397 38032 27288...
Engineering Guide Space Saver Water Cooled Performance Data Entering Water Temperature (10 Deg. Rise) Entering Air Temp. Deg. F Tons ft. H Total Sensible Total Sensible Total Sensible 27713 19584 27056 19302 26387 19018 62.5 13.1 25615 19286 24991 18994 24355 18697 13.1...
SHT� 1 OF 4 DWN BY: SHT� 1 OF 4 T� MO 2-WAY DUAL CIRCUIT 2-WAY DUAL CIRCUIT 3-WAY DUAL CIRCUIT WITH BYPASS 3-WAY DUAL CIRCUIT 2-WAY DUAL CIRCUIT Subject to change without notice. 20.3-TD (1018) WITH BYPASS UNITED COOLAIR CORP� YORK, P...
Page 10
Water-Side Economizer WITH WATER SIDE ECONOMIZER WITH BYPASS & Condenser Section ER SIDE ECONOMIZER CONDENSER SECTION 3-WAY VALVE Subject to change without notice. 20.3-TD (1018) NDENSER SECTION -WAY UNITED COOLAIR CORP� ALVE N�O� SOLENOID CONDENSING VALVE COIL YORK, PA� U�S�A�...
Page 11
Engineering Guide Space Saver Water Piping Configurations Evaporator Section Evaporator Section 2-Way Dual Circuit with Water-Side Economizer Condenser Section 2-Way Dual Circuit with ByPass & Water-Side Economizer Condenser Section Subject to change without notice. 20.3-TD (1018)
Page 12
Engineering Guide Space Saver Water Piping Configurations Evaporator Section 3-Way Dual Circuit with Water-Side Economizer Condenser Section Subject to change without notice. 20.3-TD (1018)
Engineering Guide Space Saver Correction factor for Variation in Airflow Total Sensible % of CFM Capacity Capacity 0.97 0.94 0.98 0.95 0.99 0.97 1.00 1.00 1.02 1.03 1.03 1.06 Corrects to Total for Entering Wet Bulb and also Sensible vs� Entering Dry Bulb / Wet Bulb Correction Factor for Sensible vs.
Engineering Guide Space Saver Selection Procedure Design Parameters Model: Model: VSW5G3AS Entering _________________ Entering _________________ Entering Water Temp�: _________________ Entering Water Temp�: _________________ _________________ 2200 Total _________________ Cooling: Sensible _________________ Locate data for specific model at rated conditions Example: 2000 CFM, 80 / 67 and Total _________________ 85 EWT and 15 GPM�...
Engineering Guide Space Saver Electrical Data The following sections provides the formulas and the data to calculate the Minimum Circuit Ampacity (MCA) and the Maximum Fuse Size (MOP) for your specific unit configuration. There are a variety of unit configurations. Please make sure to use the correct formulas per your configuration. It must be noted that the formulas refer to the largest motor amps�...
Engineering Guide Space Saver Electrical Data Examples Cooling Only: Package Unit NOTE: Largest motor amps may not always be the compressor� MCA = (1.25 x largest motor amps) + the sum of the remaining motors MOP = (2.25 x largest motor amps) + the sum of remaining motors Dual Compressors RLA = 19�2 each Evap�...
Engineering Guide Space Saver Electrical Data Cooling with Electric Heat: Package Unit NOTE: Largest motor amps may not always be the compressor� Electric Heat On equipment with multiple modes of operation (i�e� cooling or heating), each mode shall be evaluated and whichever load condition provides the highest value shall be used� Use the larger of the following: MCA = (1.25 x largest motor amps) + the sum of the remaining motors or MCA = (Heater FLA + Evap.
Engineering Guide Space Saver Electrical Data Compressor RLA Electrical Data: Tons Compressor (Qty) 208/230-3-60 460-3-60 Evaporator Motor FLA: Used In Tons 208/230-3-60 460-3-60 Condenser Motor FLA: Used In Tons 208/230-3-60 460-3-60 Electric Heat FLA: (Heaters nominally rated at 220 or 277 volts� Amps listed at 208, 230 and 460 volts) Nom.
Engineering Guide Space Saver Water Connections In & Out 8 – 10 Ton 1-3/8" OD 12 – 15 Ton 1-5/8" OD Notes: (1) Remote Condenser or Condensing Unit is Required for Air-Cooled Units� TONS 8 – 10 Ton 6 ¼ 11 ¾...
Page 32
FRONT VIEW RH SIDE OPTIONAL PLENUM WATER CONNECTIONS IN & OUT 8-10 TON 1-3/8" OD UNITED COOLAIR CO 12-15 TON 1-5/8" OD SUBJECT TO CHANGE WITHOUT NOTICE YORK, PA� 8-15 TON VERTICOOL TITLE: ALL PROPRIETARY RIGHTS IN THIS SPACE SAVER WITH PURCHASE ORDER/ DRAWING ARE RESERVED�...
Page 33
Engineering Guide Space Saver Water Connections In & Out 8 – 10 Ton 1-3/8" OD 12 – 15 Ton 1-5/8" OD Notes: (1) Remote Condenser or Condensing Unit is Required for Air-Cooled Units� TONS 8 – 10 Ton 6 ¼ 11 ¾...
Page 34
PLENUM LH SIDE FRONT VIEW RH SIDE WATER CONNECTIONS IN & OUT 8-10 TON 1-3/8" OD UNITED COOLAIR COR 12-15 TON 1-5/8" OD SUBJECT TO CHANGE WITHOUT NOTICE YORK, PA� 8-15 TON VERTICOOL TITLE: ALL PROPRIETARY RIGHTS IN THIS SPACE SAVER WITH...
Page 35
LH SIDE FRONT VIEW RH SIDE PLENUM WATER CONNECTIONS IN & OUT 8-10 TON 1-3/8" OD UNITED COOLAIR COR 12-15 TON 1-5/8" OD SUBJECT TO CHANGE WITHOUT NOTICE YORK, PA� 8-15 TON VERTICOOL TITLE: SEE NOTE 2 ALL PROPRIETARY RIGHTS IN THIS...
Page 36
Engineering Guide Space Saver Water Connections In & Out 2 – 3 Ton 7/8" OD 4 – 7 Ton 1-1/8" OD Notes: (1) Remote Condenser or Condensing Unit is Required for Air-Cooled Units� TONS 2 – 3 Ton ⁄ 10 ½ ⁄...
Page 37
Engineering Guide Space Saver Water Connections In & Out 2 – 3 Ton 7/8" OD 4 – 7 Ton 1-1/8" OD Notes: (1) Remote Condenser or Condensing Unit is Required for Air-Cooled Units� TONS 2 – 3 Ton ⁄ 10 ½ ⁄...
Page 38
LH SIDE FRONT VIEW RH SIDE PLENUM WATER CONNECTIONS IN & OUT 2-3 TON 7/8" OD UNITED COOLAIR COR 4-7 TON 1-1/8" OD SUBJECT TO CHANGE WITHOUT NOTICE YORK, PA� 2-7 TON VERTICOOL TITLE: ALL PROPRIETARY RIGHTS IN THIS SPACE SAVER WITH PURCHASE ORDER/ DRAWING ARE RESERVED�...
Page 39
LH SIDE FRONT VIEW RH SIDE PLENUM WATER CONNECTIONS IN & OUT 2-3 TON 7/8" OD UNITED COOLAIR COR 4-7 TON 1-1/8" OD SUBJECT TO CHANGE WITHOUT NOTICE YORK, PA� 2-7 TON VERTICOOL TITLE: ALL PROPRIETARY RIGHTS IN THIS SPACE SAVER WITH PURCHASE ORDER/ DRAWING ARE RESERVED�...
REAR VIEW LH SIDE FRONT VIEW RH SIDE WATER CONNECTIONS IN & OUT 2-3 TON 7/8" OD UNITED COOLAIR CORP 4-7 TON 1-1/8" OD SUBJECT TO CHANGE WITHOUT NOTICE YORK, PA� 2-7 TON VERTICOOL TITLE: ALL PROPRIETARY RIGHTS IN THIS...
Engineering Guide Space Saver Remote Air-Cooled Condenser I Condensing Sections Basic Model Designation EXAMPLE: “B” or “BC” Evaporator Configuration Only “B” Condensing Section w/comp. “BC” Condenser Section w/comp. “2”, “3”, “4”, “5”, “6”, “7”, “8”, “10”, “12”, “15” Nominal Cooling Capacity in Tons “G”...
Page 44
Engineered to Order LIMITED WARRANTY Authorized Distributor: United CoolAir Units are backed by a 1 year limited warranty on parts and a 5 year limited warranty on the compressor (labor not included). Maintenance items such as filters and belts are excluded under this limited warranty.