1. Use new, properly reamed pipe free from chips. If
tubing is used, make sure the ends are square,
deburred and clean. Make sure all tubing bends are
smooth and without deformation.
2. Run pipe or tubing to the gas control. If tubing is
used, obtain a tube-to-pipe coupling to connect the
tubing to the gas control.
3. Install sediment trap in the supply line to the gas
control. See Fig. 2.
Install Gas Control
1. This gas control can be mounted from 0 to 90
degrees in any direction from the vertical position of
the gas control knob.
2. Mount the gas control so gas flow is in the direction
of the arrow on the bottom of the gas control.
3. Thread pipe the amount shown in Table 5 for inser-
tion into the gas control.
IMPORTANT:
Do not thread pipe too far. Valve distortion or
malfunction can result when the pipe is inserted
too deeply into the gas control.
69-2013
DROP
PIPED
HORIZONTAL
GAS
SUPPLY
GAS
CONTROL
3 IN.
(76 MM)
MINIMUM
2
DROP
HORIZONTAL
TUBING
GAS
1
SUPPLY
RISER
3 IN.
(76 MM)
MINIMUM
2
ALL BENDS IN METALLIC TUBING SHOULD BE SMOOTH.
1
2
CAUTION: SHUT OFF THE MAIN GAS SUPPLY BEFORE REMOVING
END CAP TO PREVENT GAS FROM FILLING THE WORK AREA. TEST
FOR GAS LEAKAGE WHEN INSTALLATION IS COMPLETE.
Fig. 2. Install sediment trap.
4. Apply a moderate amount of good quality pipe com-
pound (do not use Teflon tape) to pipe only, leaving
two end threads bare. See Fig. 1. On LP installa-
tions, use compound resistant to LP gas.
5. Remove seals over gas control inlet and outlet if
necessary.
6. Connect pipe to gas control inlet and outlet. Use
wrench on the square ends of the gas control. See
Fig. 3 and 4.
Table 5. NPT Pipe Thread Length in in.
Pipe
Thread Pipe
Size
This Amount
3/8
9/16
1/2
3/4
3/4
13/16
When working with an intermittent pilot ignition system, go
to Connect Pilot Gas Tubing section next. When installing
on a hot surface or direct spark ignition system, go to the
Wiring section.
4
RISER
PIPED
GAS
SUPPLY
3 IN.
(76 MM)
MINIMUM
2
GAS
CONTROL
Maximum Depth Pipe Can
Be Inserted Into Control
3/8
1/2
3/4
GAS
CONTROL
M8435A