Table 31: Screen 527 Product Code Block - Ohmart Vega W-4510 Technical Reference Hardware Manual

Weigh scale with gen 2000 electronics model / with frequency output
Table of Contents

Advertisement

Appendix I: Parameter blocks
Item#
Parameter
Name
0
TIME CONSTANT
1
FAST RESPONSE
FILTER ENTRY
(Chrontrol)
2
SPAN
3
LINEARIZER
NUMBER
4
TEMPERATURE
COEFFICIENT
5
DENSITY TYPE
6
SOLIDS DENSITY
7
LIQUID DENSITY
8
STANDARDIZE
ABSORBER
VALUE
9
CALIBRATE HIGH
ABSORBER
VALUE
10
FREQUENCY
OUTPUT LOW
LIMIT
11
FREQUENCY
OUTPUT HIGH
LIMIT
12
LOW ALARM
LIMIT
13
HIGH ALARM
LIMIT
14
LOW-LOW ALARM
LIMIT
15
HIGH-HIGH
ALARM LIMIT
16
NUMBER OF
TABLES
17
COEFFICIENT
TYPE
18
FILTER TYPE
19
SPARE
20
SPARE
21
SPARE
22
SPARE
23
SPARE
24
SPARE
136

Table 31: Screen 527 Product code block

Parameter description
When the product code table entry #18 is set to zero, time constant is the time (in
XXXXX seconds) that 63% of a step change applied at the input of the digital
filter will appear out the output of the filter
When the product code table entry #18 is set to one, time constant defines the
number of readings to use to generate a measurement average. (100 readings
max)
When the difference between the current gauge reading and the previous gauge
reading exceeds the value of this entry, temporarily bypasses the filter
Application of gain to get normalized counts after subtraction of cal low
reference. Gain=entry/1000
Which linearizer curve to use (0–9). Normally, the curve number is the same as
the product code number. For example, Product Code #0 usually uses Curve #0,
Product Code #1 uses Curve #1, etc.
When temperature compensation enables. Entry=0.0XXXXXSGU per
degrees C or F
Enter 0=channel is not density or is straight density in SGU units. Enter
1=channel is a slurry gauge and converts to %Solids and Dry Solids. Enter
2=solutions and gives %Solids conversion
For density types 1 and 2 only
For density types 1 and 2 only
In units of product, frequency input block location 12
In units of product, frequency input block location 12
Value of data form the data pointer that gives min. analog output
Value of data form the data pointer that gives max. analog output
Setpoint for triggering a low alert
Setpoint for triggering a high alert
Setpoint for triggering a low alarm
Setpoint for triggering a high alarm
Not currently used
0=Normal (Negative) Temp Coef, 1=Positive Temp Coef
0=RC Simulation Filter, 1=Averaging Filter
W-4510 Weigh Scale Technical Reference Manual