Mounting/Installation
5
Installing the radio base SMF6120 and manual call point SMF121
54 | 82
Building Technologies
Fire Safety
Installing the manual call point SMF121
w The radio base SMF6120 is already installed.
1. Open the door of the manual call point using a suitable key.
2. Break out the opening (2) on the rear of the manual call point's housing.
3. Guide the radio base's two connection cables through the opening (2) in the
manual call point.
4.
WARNING! The manual call point does not work if the terminal assignment
deviates! Use only terminals 'b▼' and 'b▲'.
5. Clip one connection cable each to terminals 'b▼' and 'b▲' in the terminal strip.
6. Secure the manual call point to the radio base using the screws supplied.
7. Stick on the 'ATTENTION!' sign. If the feed lines are interrupted, 'Alarm
triggered' is displayed on the inside of the door of the manual call point.
8. Close the door of the manual call point.
View inside manual call point SMF121
2 Opening for cable feedthrough
WARNING
Deactivating the manual call points prevents alarms from being forwarded.
The alarm is not triggered.
●
Mark deactivated manual call points or those which are not fully functional
with the notice 'NOT IN USE'!
b
a
b
a
2
009865_m_en_--
2015-11-06