Installation Steps
1.
Mount the device on a DIN-rail inside an approved enclosure.
2.
Calculate loads to ensure any channels are not overloaded, then connect loads to the output channels. The maximum loading of this
device is as follows:
DALI Broadcast mode: max 80 drivers per channel or 300 total
DSI Mode: max 100 drivers per channel or 375 total
1-10V mode: 50mA sink or source
Note that most 1-10V cabling scenarios are polarity-dependent. DALI and DSI cables are not polarity-dependent.
3.
Connect a single phase 0.5A feed to the supply terminals. Ensure that the DDBC1200 is earthed.
4.
Connect data cables to the device as per the diagrams below.
5.
If the auxiliary dry contact input is to be used, connect a dry contact device between the AUX and GND terminals. Keep cable
runs between the DDBC1200 and the dry contact under two meters. The function of the auxiliary input is configurable via the
EnvisionProject commissioning software.
Note that correct operation of DALI Broadcast mode relies on the drivers being set to their factory defaults.
If problems are encountered, press the DDBC1200 service switch 3 times to reset all connected and energized drivers to their default
settings.
RS485 DyNet network
Recommended Cable Type
Dynalite DYNET-STP-CABLE or equivalent shielded
four twisted-pair.
See datasheet for more information.
Product Specifications
Supply:
100 - 240 VAC 50/60 Hz single phase at 0.5A
Control Outputs:
12 x HF Driver control outputs, each selectable to DALI Broadcast, 1-10V or DSI
Control Capacity:
DALI Broadcast: max 80 drivers/channel, do not exceed 300 drivers total
DSI: max 100 drivers per channel, do not exceed 375 drivers total
1-10V: 50mA sink or source
Supply Terminals:
1 x Earth, 1 x Neutral 1 x Phase
conductor size 0.2 - 5mm
Output Terminals:
12 x DALI, 0-10V, DSI driver circuits: DA+, DA-
conductor size 0.2 - 5mm
User Controls:
Manual override switch for each channel, Service switch, Diagnostic LED, programmable AUX input
Serial Port:
1 x RS485 unterminated, consisting of:
2 x RJ12 sockets
1 x 6 way terminal strip for permanent connections (2.5mm
DyNet DC supply:
12 V @ 200 mA (supply for approx. 9 user interfaces)
Presets:
170
Compliance:
CE, RCM
Operating Conditions:
Temperature: 0 to 40° C ambient
Humidity: 0 to 95% non-condensing
Storage & Transport:
Temperature: -25 to 70° C ambient
Humidity: 0 to 90% non-condensing
Construction:
Polycarbonate DIN-rail mount
Dimensions:
93 mm x 215 mm x 64 mm (3.6" x 8.5" x 2.5")
Packed Weight:
0.54 kg
Dynalite manufactured by WMGD Pty Ltd (ABN 33 097 246 921) Unit 6, 691 Gardeners Road Mascot NSW 2020 Australia Tel: +61 2 8338 9899 Fax: +61 2 8338 9333
E-Mail: support.controls@philips.com
Recommended Cable Color Coding
Green/White Pair
Orange/White Pair
Blue/White Pair
Brown/White Pair
(24 - 10 AWG)
2
(24 - 10 AWG)
2
DDBC1200 Installation Instructions Rev 08 Specifications subject to change without notice
Paralleled for GND
Paralleled for +12VDC
Blue for DATA+
White for DATA-
Spare, use for SHIELD on unshielded cables
conductor size)
2
Web: http://philips.com/dynalite
Shield
Green/Green white
Blue
Blue white
Orange/Orange white
Brown/Brown white

Advertisement