AMC2 enclosure - 1 DIN
rail
The components described below refer to Figure 1.1:
Cable 12 - AC Power Cable
Connect the 2-pin plug 13 on the interface AC of the power
supply.
Cable 5 – Tamper Cable
Connect the loose ends of the cover tamper switch to the 2-pin
screw connector on the top of the AMC marked with T. Position
the cable in the space between the housing and the mounting
rail.
Danger!
Risk of electric shock
Make sure that all wires to be connected have Zero potential!
Main AC supply X:
1.
2.
3.
Notice!
Shorten the external supply wires so that the ground (yellow/
green) wire is at least 20 mm (0.8 in.) longer than the live (blue
and brown) wires. This ensures that the ground wire cannot be
accidentally disconnected before live wires.
Cable 1 – Cover grounding Cable
1.
2.
Bosch Access Systems GmbH
Connect the grounding cable to the housing at position 8 in
figure 1.1.
Connect the blue (neutral) wire to terminal N.
Connect the brown (phase) wire to terminal L1.
Connect cable 1 to the grounding point on the cover.
Close the cover.