4. Connect and Route the Audio Cable for Two-way Voice (if used)
The communicator requires an optional audio cable (GSMV-AUDIO, grey) to support two-way
voice using an AVS Base Unit. Note the AVS Base Unit is part of Honeywell's AVS Audio
Verification System. This system consist of the AVS Base Unit, Remote Station, and the
Remote Station PC board. For detailed information, please refer to the AVS Audio Verification
System documentation. Follow the guidelines below for connecting the audio cable.
1. Power down the communicator, control panel and AVS Audio Verification System. (When
the communicator is fully wired up, restore power to the control panel and AVS Audio
Verification System.)
2. Connect one end of the audio cable to the audio connector located on the small PC board.
3. Route the audio cable to the connector on the AVS Base Unit and connect the cable.
4. Ensure the audio cable ends are secured with tie wraps to reduce strain.
5. Setup the Account, Activate the SIM, Program, and Register the Communicator
SETUP THE ACCOUNT
To setup the customer account you will need to contact the central monitoring station to get
account information, and have access to the AlarmNet Direct website. To access the AlarmNet
Direct website visit – https://services.alarmnet.com/AlarmNetDirect
If you do not wish to use the AlarmNet Direct website, you may call AlarmNet to setup the
account; just phone 800-222-6525, then select option 1.
(Monday–Friday 8:00 am to 9:00 pm, Saturday 9:00 am to 5:30 pm EST)
Have the following information ready:
Primary City ID (two digits),
obtained from your monitoring
station.
Primary Central Station ID (two
digits), obtained from your
monitoring station.
ACTIVATE THE SIM
Note: The communicator comes with a SIM (Subscriber Identity Module) that needs to
be activated. The GSMVCN4G and IGSMVCN4G come already activated.
To activate the SIM, log into the AlarmNet Direct website. (Refer to the online help if needed.)
Enter the required information, then activate the SIM.
PROGRAM THE COMMUNICATOR
Using the AlarmNet Direct website:
Log in as you did to activate the SIM and complete the communicator programming using the
"Program New Device GSM/I" tool. (Refer to the online help if needed.)
When complete you may log out of the AlarmNet Direct website.
Warning – The internal or external antenna(s) used with this product must be installed to provide a separation distance of at least 7.8 in. (20 cm) from all persons and must not be co-located or operating in
conjunction with any other antenna or transmitter except in accordance with FCC multi-transmitter product procedures.
Exposition aux Frequences Radio: L'antenne (s) utilisée pour cet émetteur doit être installée à une distance de séparation d'au moins 7,8 pouces (20 cm) de toutes les personnes.
Ê800-11796oŠ
800-11796 5/12 Rev. D
Primary Subscriber ID (four digits), obtained from
your monitoring station.
Communicator's MAC ID, and MAC CRC number is
located on the box and inside the communicator.
2 Corporate Center Drive, Suite 100, P.O. Box 9040, Melville, NY 11747
Copyright  2012 Honeywell International Inc.
Using the 7720 Programming Tool:
Ensure the system is powered up and connect the programming tool to the communicator. Accept all
default settings except the following prompts which need to be answered. Then exit the
programming mode.
Press [#].
Device Mode ECP
Enter number 01-99, then press [#].
Primary City ID (??)
Enter number 01-FE, then press [#].
Primary CS ID (??)
Enter number 0001-9999, then press [#].
Primary Sub ID (????)
Accept the default by pressing [#], or change if this address
Device Address (03)
is already used.
The following prompt appears for the IGSMV4G and IGSMVCN4G only.
Press [] to scroll, choose Notify Panel of Both IP&GSM
Notify Panel of Neither
Flts, then press [#].
Fault
REGISTER THE COMMUNICATOR
Registering the communicator activates the account with AlarmNet and enables the control panel to
send reports. There are three ways to register the communicator:
• You can register by logging into AlarmNet Direct choosing "Show Programmed Devices GSM/I"
tool. Search for the account using the Account Information or MAC ID. Under the "Actions"
column, use the pulldown menu select "Register" the account.
• After the communicator is installed and programmed, you can register by clicking the Tamper
Switch 3 times.
• After the communicator is installed and programmed, you can register by using the 7720P
Programming tool. Simply: Press [Shift ] then press []. Please wait for "Registration SUCCESS"