RKI Instruments 61-1001RKSS Operator's Manual

Hydrogen detector

Advertisement

Quick Links

61-1001RKSS
Hydrogen Detector
Operator's Manual
Part Number: 71-0229RK
Revision: P1
Released: 1/11/18
www.rkiinstruments.com

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 61-1001RKSS and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for RKI Instruments 61-1001RKSS

  • Page 1 61-1001RKSS Hydrogen Detector Operator’s Manual Part Number: 71-0229RK Revision: P1 Released: 1/11/18 www.rkiinstruments.com...
  • Page 2 Typical calibration frequencies for most applications are between 3 and 6 months, but can be required more often or less often based on your usage. 61-1001RKSS Hydrogen Detector...
  • Page 3 Product Warranty RKI Instruments, Inc. warranties gas alarm equipment sold by us to be free from defects in materials, workmanship, and performance for a period of one year from date of shipment from RKI Instruments, Inc. Any parts found defective within that period will be repaired or replaced, at our option, free of charge.
  • Page 4: Table Of Contents

    Parts List ..............11 61-1001RKSS Hydrogen Detector...
  • Page 5: Overview

    WARNING: When using the 61-1001RKSS, you must follow the instructions and warnings in this manual to assure proper and safe operation of the 61-1001RKSS and to minimize the risk of personal injury. Be sure to maintain and periodically calibrate the 61-1001RKSS as described in this manual.
  • Page 6: Description

    Description This section describes the components of the NC-6205-01 and 61-1001RKSS detectors. The 61-1001RKSS includes the NC-6205-01 hydrogen detector and a junction box. A four point terminal strip is provided inside the junction box for detector connections. Green Black White...
  • Page 7: Installation

    .20 Dia. x .45 Slot, 2X 7.40 MAX J-Box Hydrogen Detector Figure 2: Mounting the Hydrogen Detector At the mounting site you select, hang or mount the junction box with the detector facing down (see Figure 2). 61-1001RKSS Hydrogen Detector • 3...
  • Page 8: Wiring The Hydrogen Detector

    61-1001RKSS detector. If using shielded cable, connect the cable’s drain wire to an available chassis ground at the controller. RKI controllers typically have a ground stud that is a convenient grounding location. 4 • 61-1001RKSS Hydrogen Detector...
  • Page 9 White Controller LEL Detector Terminals Green Black J-Box Terminal Strip Black Green Detector Wires White Hydrogen Detector Figure 3: Wiring the Hydrogen Detector to a Controller 61-1001RKSS Hydrogen Detector • 5...
  • Page 10: Startup

    If the display reading is 0% LEL, start up is complete. The hydrogen detector is in normal operation. If the display reading is not 0% LEL, continue with step 3. Perform a zeroing operation at the controller. See the controller operator’s manual for directions. 6 • 61-1001RKSS Hydrogen Detector...
  • Page 11: Maintenance

    Use the calibration kit sample tubing to connect the regulator to the calibration cup. Performing the response test Turn the regulator’s on/off knob counterclockwise to open the regulator. Gas will begin to flow. Allow the gas to flow for one minute. 61-1001RKSS Hydrogen Detector • 7...
  • Page 12: Troubleshooting

    • Detector requires 4. If the calibration/response difficulties frequent calibration. continue, contact RKI for further instruction. Note: Under “normal” circumstances, the detector requires calibration once every three months. Some applications may require a more frequent calibration schedule. 8 • 61-1001RKSS Hydrogen Detector...
  • Page 13: Replacing The Hydrogen Detector

    Connect the detector leads to the terminal block the same way the old detector was wired (see Figure 3). See the controller operator’s manual and the controller’s detector head specification sheet for the 61-1001RKSS detector to verify the connections to the controller are correct.
  • Page 14: Calibration

    When the directions call for exposing the detector to gas, turn the regulator’s on/off knob counterclockwise to open it. Allow the gas to flow for one minute before continuing with the directions. After setting the response reading, turn the regulator’s on/off knob clockwise to close 10 • 61-1001RKSS Hydrogen Detector...
  • Page 15: Returning To Normal Operation

    Verify that the controller display reading decreases and stabilizes at 0 %LEL. Store the components of the calibration kit in a safe and convenient place. Parts List Table 3 lists replacement parts and accessories for the 61-1001RKSS hydrogen detector. Table 3: Parts List Part Number...

Table of Contents