COMPACT I/O MODULE
nvoHigh_1...8
When exceeding the temperature set in UCPTHighT the
output variable changes from 0,0 0 to 100,0 1. When under-
running the temperature set in UCPTHighT plus the hysteresis
set in UCPTHyst the output variable changes from 100,01 to
0,0 0.
UCPTSensor_tab
Temperature
° F (° C)
Factory setting: NTC20k in the range-22° F to 266° F (-30° C to +130° C).
UCPTTempMax
UCPTTempMin
The temperature output variables are calculated during
voltage measurings according to a 0 to 10 Volt input signal
and the here selected range.
®
®
®
LON
, LonMark
, LNS
and Echelon
95-7716—1
SNVT_switch
Resistance
SNVT_temp Werk:
+ 302° F (+150° C)
SNVT_temp Werk:
- 58° F (-50° C)
®
are registered trademarks of Echelon Corporation.
nvoLow_1...8
When under-running the temperature set in UCPTLowT the
output variable changes from 0,0 0 to 100,0 1. When
exceeding the temperature set in UCPTLowT plus the
hysteresis in UCPTHyst the output variable changes from
100,0 1 to 0,0 0.
UCPTTemp_Offset
The respective measurand can be readjusted in steps of 0.1 K.
Sensor Name
UCPTHighT
UCPTLowT
Setting of the thresholds nvoHigh and nviLow to make the
switch variables switch over.
SCPTinvrtOut
Inverting the values at nvoHigh or nvoLow.
6
SNVT_switch
SNVT_temp
ST_ON
ST_OFF
(Resistance)
(Voltage)
SNVT_temp Werk:
+212° F (+100° C)
SNVT_temp Werk:
-14° F (-10° C)
SNVT_lev_disc