6 CE LIMITATIONS
6.1 Operation environment and shielded wiring
The operating conditions for components are as follows:
Attributes
Storage temperature:
Ambient temperature (T4)
Relative humidity:
Vibration (sinosoidal):
Shock
Shielded wiring required
Ethernet cables are used in cabinets to interconnect C300 Controller IOTAs. Only a shielded twisted pair (STP)
type cable is used. The use of unshielded twisted pair (UTP) cable is not allowed.
26
www.honeywell.com
Values
-40°C to +85°C (–40°F to +185°F)
0°C to +60°C (32°F to +140°F)
5% to 95% (non-condensing)
Excitation: sine-shaped with sliding frequency
•
Frequency range: 10-150 Hz
•
Loads: 10 Hz— 57 Hz: 0.075 mm
•
Loads: 57 Hz-150 Hz: 1 G
•
Number. of axes: 3 (x, y, z)
•
Traverse rate: 1 oct/min.
15 G in 3 axes (shock duration: 11 ms)