12 SPECiFiCATiONS
12
SPECIFICATIONS
TORKEL 900-series
Specifications are valid at nominal input voltage and an ambient
temperature of +25°C, (77°F). Specifications are subject to change
without notice.
Environment
Application field
The instrument is intended for use in high-
voltage substations and industrial environ-
ments.
Temperature
Operating
0°C to +50°C (32°F to +122°F)
Power derating at temperatures over +35°C
(+95°F)
Storage & transport -40°C to +70°C (-40°F to +158°F)
Humidity
5% – 95% RH, non-condensing
Shock/Vibration/Fall
Instrument only
ETSi EN 300 019-2-7 class 7M2
Instrument in
iSTA 2A
transport case
Altitude
Operating
3000 m (10000 ft)
Storage
10000 m (33000 ft)
Encapsulation class
iP20
CE-marking
LVD
iEC61010-1:2010 & iEC61010-2-030
EMC
iEC61326-1
General
Mains voltage
100 – 240 V AC, 50 / 60 Hz
Power consumption
200 W (max)
Power interruption
40 ms (max)
Protection
Thermal cut-outs, Automatic overload pro-
tection, Emergency stop button
Dimensions
519 x 315 x 375 mm, (20.5" x 12.4" x 14.7")
Weight
19.5 kg (43.0 lbs) instrument
31.9 kg (70.3 lbs) incl. standard transport case
37 kg (82 lbs) incl. large transport case
Display
7" LCD, Capacitive touch screen
Available languages
English, French, German, Spanish, Swedish
Measurement section
Current measurement
Display range
0.0 to 2999.0 A
Basic inaccuracy
±(0.5% of reading +0.1 A)
Resolution
0.1 A
Internal current measurement
Range
TORKEL 910
0 to 110 A
TORKEL 930 / 950
0 to 220 A
Input for clamp-on probe
Range
0 to 1000 mV DC
mV/A-ratio
0.30 mV/A to 100.00 mV/A
Input impedance
>1 MΩ
46
TORKEL 900-SERiES
Specifications
Voltage measurement
Voltage
0 to 500 V DC
Inaccuracy
±(0.5% of reading +0.1 V DC)
Resolution
0.1 V
Sample rate
10 Hz, Values are saved when change is >10 mV
Time measurement
Inaccuracy
±0.1% of reading ±1 digit
Load section
Battery voltage
7.5 V to 300 V
Power
15 kW (max)
Load patterns
Constant current, constant power, constant
resistance, current or power profile
Constant I
Range
TORKEL 910
0 to 110.0 A
TORKEL 930 / 950
0 to 220.0 A
Inaccuracy
±(0.5% +0.2 A)
Resolution
0.1 A
Ripple
max 0.5 A peak
Constant R
Range
300 mΩ to 3 kΩ
Inaccuracy
±1% typical
Resolution
100 mΩ
Constant P
Range
0 to 15 kW
Inaccuracy
±1% typical
Resolution
10 W
Inputs
+
7.5 to 300 V
–
0 V
I EXT ≤ 1 V
1 V DC, 300 V DC to ground
VOLTAGE SENSE
impedance to the current terminals is >1 MΩ
ZP-CS01E
1)
/ 500 V
2)
1)
2)
7.5 to 500 V
.
.
CS033663DE