Document: UM-1021
1
S2
1
RS-R85 / ETHERNET OPTION
U3
U2
P1
*SENSOR INPUT OPTION
Combination Cat-bead/Toxic = 10-0216
Dual Cat-bead = 10-0219
Dual Toxic = 10-0220
Dual 4-20mA = 10-0221
*Each Input option listed may also
be configured for 4-20mA Inputs.
See drawings for details on each.
TB1
1
+
DC PWR
SUPPLY
INPUT
3 Watts MAX
TB1
TB2
Available for 10-30VDC
Dry contact input for use
primary power input.
with optional remote
May also be used as
Alarm Reset switch.
battery back-up to AC
Wires must be shorter
primary power source.
than 10 feet & shielded
TIE TB5 GND to EARTH
if longer than 2 feet.
ViewSmart 200/2050/2150 Controller User's Manual
Universal Switching Power Supply
PS1
Ribbon Cable to 10-0214 Display Assembly
S1
P2
4-20mA OUTPUT OPTION
(See dwg. 10-0223)
TB2
J2
2
1
2
1
-
+
-
+
-
ALARM
AUDIBLE
RESET
ALARM OPTION
J2
+Terminal = 24 VDC
24 VDC power output
- Terminal is open
for remote devices such
collector 100mA driver
as transmitters, lights,
for use with optional 100
relays etc. 350mA MAX
decibel piezo
(see Figure 3.0)
annunciator.
Figure 3.1
21
0010-1167 Rev C
2-Channel Controller
MotherBoard
U5
Connections to J1 & J3 are not covered by CSA
-
D1
RELAY 1 Indicator
D2
RELAY 2 Indicator
WARNING: For continued protection against
fire replace only with same type and rating
of fuse. (Part # = Littelfuse 217002)
K1
TB3
TB4
1
2
1
2
3
4
5
6
+
-
C
C
N/O
N/C
N/O
N/C
AUX
RELAY 1
RELAY 2
POWER
DRY CONTACTS
OUTPUT
TB3
TB4
5 amp resistive SPDT
(form C) dry contact relay
outputs. Use appropriate
diode / snubber devices
when switching inductive
loads.
Revision Level B
Assy.10-0215
CR5
DATA-LOGGER PORT
J3
J1
Common
TP1
(0-volts)
P3
DISCRETE RELAY OPTION
(See dwg. 10-0222)
Note: If installed, this option
blocks access to the fuse and
must be removed to replace fuse.
K2
2-AMP FUSE
(5 x 20mm)
TB5
1
2
3
L1
L2
GND
~
100-240 VAC
.45A 50/60 Hz
AC POWER
TB5
Universal 100-240VAC
primary power source
terminals.
Important: GND terminal
3 must be tied to earth
for correct shielding of
incoming signals.
SHOCK HAZARD
RISK OF ELECTRICAL
SHOCK-DISCONNECT OR
TURN OFF POWER
BEFORE SERVICING THE
EQUIPMENT