When Cooling Operation Does Not Work; When Healing Operation Does Not Work - Mitsubishi Electric MXZ-2F33VF-E1 Service Manual

Outdoor unit, hfc utilized, r32
Hide thumbs Also See for MXZ-2F33VF-E1:
Table of Contents

Advertisement

MXZ-3F54VF/3F68VF/4F72VF
1. Disconnect the lead wire leading to the compressor.
2. 3 minutes after turning ON the power supply, start EMERGENCY
OPERATION in COOL mode.
Is there voltage of 220 - 230 - 240 V AC
between pin1 and pin2 at connector CN712?
Yes
Turn OFF the power supply.
Disconnect the connector CNAC2.
Is there normal resistance
to R.V. coil? (Refer to 12-5.)
Yes
Replace the 4-way valve.
1. Disconnect the lead wire leading to the compressor.
2. 3 minutes after turning ON the power supply, start EMERGENCY
OPERATION in HEAT mode.
Is there voltage of 220 - 230 - 240 V AC between
pin1 and pin2 at connector CN712?
Yes
Replace the outdoor control P.C. board.
OBH790
Is there voltage 220 - 230 - 240 V AC
No
between the pin1 and pin3 at
connector CNAC?
No
Replace the R.V. coil.
No
Yes
Replace the outdoor
control P.C. board.
Replace the 4-way valve.
75
Connector
MXZ-3F, 4F
CNAC
Outdoor control
CN712
P.C. board
Outdoor power
CNAC2
P.C. board
No
Replace the outdoor
power P.C. board.