AMC2 Extensions
Examp
le
using more than two Extensions this combination is
recommended
4
Table 4.1: Overview - power supply and power consumption
Explanations for the table columns:
Output power
Own usage
Available
Constant load
Hence Example 1 can be read as follows:
Of the total incoming power (60VA) 5VA will be drawn by the
AMC2 itself . This leaves 55VA to support external devices.
25VA of these 55VA can be used for constant load (e.g. a card
reader) leaving 30VA for occasional peak usage (e.g. a door
opener).
Bosch Sicherheitssysteme GmbH
Used
components
PS + AMC2 +
Extension
and
PS + Extension +
Extension
Power provided by the power supply.
Power used by AMC2 device
Power remaining for external devices
Amount of the available power that can
be drawn constantly.
Output
Own
power
Usage
60VA
2 x
+
5VA
60VA
+
2 x
5VA
Installing | en
availabl
Constan
e
t load
50VA
20VA
+
+
50VA
20VA