Flame Signal Monitoring; Real Flame Current Versus Reading On Frontal Jack Plug; Std & Enh Models (Flame Detector Select Only); Ult Model (Bus Connector And Address Switches) - Honeywell DBC2000E10 Series Handbook

Digital burner controller, dbc2000 series
Hide thumbs Also See for DBC2000E10 Series:
Table of Contents

Advertisement

Flame signal monitoring

Note:
The flame signal strength on the flame current jack plug is only for reference and can vary between different
DBC2000 devices.
When measuring the flame signal current directly in the flame sensor wiring whilst:
1. Using a flame rod, the (multi-)meter will show the real flame current in µA.
2. Using a UV sensor (C7027, C7035 or C7044), the current in the sensor lead wires will be in the range of
20...25mA (inverted values).
Fig. 4-3: Measuring flame signal with multi meter (µA range selection) using a jack plug.
STD & ENH Models (flame detector select only)
Fig. 4-4: Position of flame sensor selection jumpers and bus connector on the back of the DBC2000.
Fig. 4-2: Real flame current versus reading on frontal jack plug.

ULT Model (bus connector and address switches)