System Operation - Amana GMS8 Service Instructions Manual

80% single stage gas furnaces & accessories
Hide thumbs Also See for GMS8:
Table of Contents

Advertisement

SYSTEM OPERATION

HEATING - Abnormal Operation
The following presents the probable causes of question-
able furnace operation and how to fix them. Look through
the observation window in the blower access door and make
a note of the number of flashes in sequence between pauses.
Next, refer to the Troubleshooting Chart on the following
pages for an interpretation of the LED signals and to the
information in this section for a description of the problem.
1. Internal Control Failure with Integrated Ignition
Control. Check for voltage to the furnace and low volt-
age at the control board. Check for blown fuse on the
control board. If the control determines it has an inter-
nal fault, it enters a locked-out state. Any of the situa-
tions mentioned will cause the diagnostic LED to pro-
vide no signal. The control board should only be re-
placed after all other checks from the Troubleshooting
Chart have been verified.
2. System Lockout. If a flame is not sensed during the
first seven (4) seconds after the gas valve is energized,
the control turns off the gas. There will then be a 30
second delay while the induced draft blower is ener-
gized to purge the heat exchanger. The ignitor will next
be energized and preheated for (8) seconds. The gas
valve will then be energized. If flame is not sensed in
seven (4) seconds the gas valve will be de-energized
and another purge will occur. The control will cycle the
gas valve a total of three (3) times before it determines
it cannot establish measurable combustion and enters
a locked out state. The diagnostic light code for this
problem is one short flash followed by a longer pause.
The control can be reset and brought out of lockout
mode by turning the thermostat off for more than (5)
seconds and less than (20) seconds and then back on.
It can also be reset by turning off the electrical discon-
nect switch to the furnace for a minimum of 5 sec-
onds.
NOTE: The control board will automatically reset one hour
after lockout occurs. If the furnace frequently has to be
reset, it means that a problem exists that should be cor-
rected. Refer to Troubleshooting Chart on the following
pages for aid in determining the cause.
3. Pressure Switch Stuck Closed. If the control senses
the pressure switch is closed when the induced draft
blower is off, it waits until the fault is corrected. The
diagnostic light code for this problem is two short
flashes followed by a longer pause. The probable cause
is either a faulty pressure switch or wiring.
42
(PCBBF123 Control Board)
4. Pressure Switch Stuck Open. If, after the induced draft
blower is energized, the pressure switch does not close
within 5 minutes, the control will go into a 1-hour lock-
out. The control will automatically reset from lockout adn
restart the ignition sequence. The diagnostic light code
for this problem is three short flashes followed by a
pause. The probable causes are either disconnected
hose to the pressure switch, faulty pressure switch or
wiring, or restricted air intake or flue piping.
5. Open Primary Limit. If the limit control opens, the air
circulator blower will be turned on until the limit closes.
The induced draft blower will turn off for 5 seconds then
turn off. The diagnostic light code for this problem is four
short flashes followed by a pause. The probable cause
is either low conditioned air flow due to dirty filter or re-
sistance in duct work, faulty limit, faulty blower, or blower
speed set to low.
6. Flame Sensed with No Call for Heat. If the control
senses a flame when the gas valve is de-energized, it
will run the air circulation blower and the induced draft
blower continuously with no further furnace operation.
The diagnostic flash code for this is a five flashes. The
probable causes are either a short to ground in flame
sense circuit, miswiring, lingering burner flame or a slow
closing gas valve.
7. Open Rollout Limit. If the rollout control opens, the air
circulator blower will be energized all the time. The diag-
nostic light code for this problem is six flashes followed
by a pause. The probable cause is either restricted flue
piping or improper air requirements.
8. Low Flame Sense Signal. If the furnace continues to
operate and the micro-amp signal from the flame sensor
falls below specified level, the diagnostic light code for
this problem will be seven flashes followed by a pause.
The probable cause is either a coated/oxidized sensor,
incorrectly positioned senser in burner flame or lazy
burner flame due to improper gas pressure or combus-
tion air.
9. Igniter circuit or poor ground. Improperly connected
igniter, bad igniter or poor ground to the equipment. The
diagnostic light code for this problem is eight flashes.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vds8Ams8Gds8Adss8Vms8

Table of Contents