Example Of Safety System Configuration - Mitsubishi Electric FR-A800 Instruction Manual

Hide thumbs Also See for FR-A800:

Advertisement

3
EXAMPLE OF SAFETY SYSTEM
CONFIGURATION
●FR-A800/F800 configuration example
Emergency
stop button
+24V
X0
X1
COM0
Internal
24V
Safety
DC
Circuit
24G
S a f e t y r e l a y module
M E L S E C Q S 9 0 S R 2 S N-Q
∗1 When the control logic is the sink logic, the common terminal is terminal SD.
Figure 4 Safety system example of the FR-A800/F800 inverter
NOTE
• When starting up the system operation, press the RESET switch to reset the safety stop function first,
then turn ON the START switch to run the motor.
• In the above configuration, after resetting the of emergency stop button, the inverter will be in the safe-
state until the RESET switch is pressed.
Caution
 To prevent restart of the inverter when the power is restored after a power failure, 3-wire connection
is recommended for the START/STOP control. In case of 2-wire connection and using latching type
switch to short between STF and SD/PC for starting, ensure the compliance with safety standards for
the restarting when the inverter power is restored after a power failure.
So (SO)
SOC
RESET
START
STF
STOP
STOP
S 2
24V
DC
XS0 XS1
Z00
Z10
Z20
COM1
S 1
K1
SIC
K 2
SD
Z01
Z11
Z21
PC *1

EXAMPLE OF SAFETY SYSTEM CONFIGURATION

Logic
CPU
ASIC
+24V
Fuse
FR-A800/F800
R/L1 S/L2 T/L3
Gate
Gate
Drive r
Drive r
IGBTs
G
G
U
V
W
M
9