Mitsubishi Electric FR-A7ND Instruction Manual page 51

Inverter plug-in option devicenet communication function 700 series
Hide thumbs Also See for FR-A7ND:
Table of Contents

Advertisement

OBJECT MAP
[Instance 126 details]
Bit0
Bit1
Bit2
Fault Reset
Bit5
Byte0
Bit6
Bit7
Write Param
Byte1
Instance No.
Byte2
Byte3
Byte4
Byte5
Attribute ID
44
Run Fwd
Forward rotation signal (0:forward rotation off 1:forward rotation on) Control related
Run Rev
Reverse rotation signal (0:reverse rotation off 1:reverse rotation on)
Reset request at an error occurrence
Valid only at in inverter trip
(0:no function 1:fault reset request)
Request permission bit of control related signals (Bit 0 to Bit 2)
NetCtrl
0: Control related signals are invalid (It will not function even if bit is set.)
1: Control related signals are valid (It will not be reflected to Pr. 338.)
Request permission bit of speed reference (Byte 2, Byte 3)
NetRef
0: Speed setting value (Byte 2, 3) is invalid (It will not function even if a value is set.)
1: Speed setting value (Byte 2, 3) is valid (It will not refflected to Pr. 339.)
Request permission bit of speed reference or parameter write (Byte 2, Byte 3)
0: Byte 2, 3 are speed reference
1: Byte 2, 3 are written to parameter write data (It is written to parameter class and
attribute set with Byte 4, 5.)
Parameter
Instance No. can be specified.
When 00 is specified, instance No. is regarded as 1.
Speed reference (r/min) or parameter write data
Selection conditions are determined according
to a combination of "NetRef (Bit 6)" and
Speed Ref
"WriteParam (Bit 7)".
[When speed reference is selected]
Conversion of speed and frequency depends on
the Pr. 144 settting.
Parameter
Class ID to access to the inverter parameter (class 0x2A, 0x66, 0x67 etc.)
Class ID
Parameter
Attribute ID to access to the inverter parameter
signals
Only NetCtrl (Bit
5) = 1 is valid.
Write
Net
Selected Data
Param
Ref
0
0
0
1
Speed reference
1
0
Parameter write
data
1
1