Address Space - Siemens Simatic ET 200MP Manual

Digital input module (6es7521-1bl00-0ab0)
Hide thumbs Also See for Simatic ET 200MP:
Table of Contents

Advertisement

4.2

Address space

The module can be configured differently in STEP 7; see following table. Depending on the
configuration, additional/different addresses are assigned in the process image of the inputs.
The letters "a to d" are printed onto the module. "EB a" for example, stands for module start
address input byte a.
Configuration options of DI 32x24VDC HF
You can configure the module with STEP 7 (TIA Portal) or with a GSD file.
When you configure the module by means of the GSD file, the configurations are available
under different abbreviations/module names.
The following configurations are possible:
Table 4- 3
Configuration options
Configuration
1 x 32-channel without value status
1 x 32-channel with value status
4 x 8-channel without value status
4 x 8-channel with value status
1 x 32-channel with value status for
module-internal Shared Input with up to 4
submodules
1 x 32 channel with value status (channel
0 and channel 1 for counting, channels 2
to 31 as digital inputs).
Value status (Quality Information, QI)
The value status is always activated for the following module names:
● DI 32x24VDC HF QI
● DI 32x24VDC HF S QI
● DI 32x24VDC HF MSI
● DI 32x24VDC HF Count
An additional bit is assigned to each channel for the value status. The value status bit
indicates if the read in digital value is valid. (0 = value is incorrect).
DI 32x24VDC HF digital input module (6ES7521-1BL00-0AB0)
Manual, 09/2016, A5E03485935-AF
Short designation/
module name in the
GSD file
DI 32x24VDC HF
DI 32x24VDC HF QI
DI 32x24VDC HF S
DI 32x24VDC HF S QI
DI 32x24VDC HF MSI
DI 32x24VDC HF Count
Parameters/address space
Configuration software, e.g., with STEP 7
(TIA Portal)
Integrated in hardware
catalog STEP 7
(TIA Portal)
V12 or higher
V12 or higher
V13 update 3 or higher
(PROFINET IO only)
V13 update 3 or higher
(PROFINET IO only)
V13 update 3 or higher
(PROFINET IO only)
V13, SP1 with HSP
0118 or higher
4.2 Address space
GSD file in
STEP 7 (TIA Portal) V12
or higher or STEP 7 V5.5
SP3 or higher
X
X
X
(PROFINET IO only)
X
(PROFINET IO only)
X
(PROFINET IO only)
X
(PROFINET IO only)
21