Electrical Diagram
Supply:
100-240V
1 Phase
0.25A
N L IN OUT
E
µP
Data Cable Connection
RS485 DyNet network
Recommended Cable Type
Dynalite DYNET-STP-CABLE or equivalent shielded
three twisted-pair.
See datasheet for more information.
Product Specifications
Control Supply:
Load Outputs:
Switching Device:
Supply Terminals:
Load Terminals:
User Controls:
I/O:
DyNet DC Supply:
Presets:
Programmable Logic:
Operating Conditions:
Storage & Transport:
Construction:
Dimensions:
Weight:
Certification:
Dynalite manufactured by WMGD Pty Ltd (ABN 33 097 246 921) Unit 6, 691 Gardeners Road Mascot NSW 2020 Australia Tel: +61 2 8338 9899 Fax: +61 2 8338 9333
CH4
CH1
CH2
CH3
IN OUT IN OUT IN OUT IN OUT IN OUT IN OUT IN OUT IN OUT IN OUT IN OUT IN OUT
100-240 V 50/60 Hz single phase at 0.25 A, Over-voltage category III, maximum 4kV surge
12 x feed-through outputs at 20 A per channel, maximum total device load 180 A
1 Phase & Neutral, 3 Phase & Neutral Star. Some delta wiring supported.
Relay 50 A 230 VAC resistive (5000 VA lighting load rated), maximum 500 A (200 uS) inrush current
1 x Phase, 1 x Neutral 1 x Earth, up to 5 mm
1 x Phase, 1 x Neutral 1 x Earth, up to 5 mm
Service switch, Diagnostic LED
1 x RS485 DyNet serial port
1 x AUX programmable dry contact input
120 mA (capacity for approximately six panels)
170
8 tasks (most UPAN mnemonics supported)
Temperature: 0 to 50° C ambient, Humidity: 0 to 90% non-condensing
Temperature: -25 to 60° C ambient, Humidity: 0 to 90% non-condensing
Polycarbonate DIN-rail enclosure, (12 units wide), IP20, UL940-V0 rated
93 mm x 215 mm x 64 mm (3.7" x 8.5" x 2.5")
0.76 kg
CE, RCM
DDRC1220FR-GL Installation Instructions Rev 08 Specifications subject to change without notice
E-Mail: support.controls@philips.com
CH5
CH7
CH8
CH6
Recommended Cable Color Coding
Green/White Pair
Orange/White Pair
Blue/White Pair
Brown/White Pair
cable per terminal
2
cable per terminal
2
Web: www.philips.com/dynalite
CH9
CH10
CH11
CH12
2 x RJ12
DyNet
RS485
Paralleled for GND
Paralleled for +12VDC
Blue for DATA+
White for DATA-
Spare, use for SHIELD on unshielded cables
Shield
Green/Green white
Blue
Blue white
Orange/Orange white
Brown/Brown white