Output Function
The alarms can be set to function in the desired mode.
Function
1 *
2
3
4
5
6
7
8
9
10
11
12
13
14
* Factory setting
Function display:
high alarm
high-high alarm
low alarm
low-low alarm
loss of echo alarm
pump up control
pump down control
Setpoints
The setpoints can be set where reference levels,
either from the material in the vessel or from a
target, cannot be provided. This method can also
be used to trim the output levels obtained by the
Reference Method (Quick Start).
The setpoints are referenced from the face of the
sensor. They should not be set at or above the
blanking value, or at or below the range limit.
Factory Setting: Relay 1 = 0.5 m (1.64 ft)
Relay 2 = 4.50 m (14.76 ft)
Page EN-14
Relay 1
high alarm
high alarm
low alarm
high alarm
low alarm
pump down
pump down
pump up
pump up
pump down
pump up
pump down
pump down
pump up
H
HH
L
high-high
LL
high
LOE
PU
PD
low
low-low
setpoint
Pointek ULS200 – QUICK START MANUAL
Relay 2
low alarm
high alarm
low alarm
LOE alarm
LOE alarm
low alarm
high alarm
low alarm
high alarm
LOE alarm
LOE alarm
pump up
pump down
pump up
ULS200
blanking
range
limit
A5E32268616