Download  Print this page

Setting Items And Set Data - Mitsubishi Electric FR-CS84-012 Instruction Manual

Freqrol-cs80.
Hide thumbs

Advertisement

 Setting items and set data
• After completion of parameter settings, set the instruction codes and data, then start communication from the computer to
allow various types of operation control and monitoring.
Read/
Instruction
Item
write
Read
H7B
Operation mode
Write
HFB
Output
Read
H6F
frequency /
Output current
Read
H70
Output voltage
Read
H71
Special monitor Read
H72
Read
H73
Special monitor
selection No.
Write
HF3
Fault record
Read
H74 to H77
Operation
command
Write
HF9
(extended)
Operation
Write
HFA
command
Inverter status
Read
H79
monitor (extended)
Inverter status
Read
H7A
monitor
Set frequency
H6D
(RAM)
Read
Set frequency
H6E
(EEPROM)
Set frequency
HED
(RAM)
Write
Set frequency
HEE
(RAM, EEPROM)
code
H0000: Network operation
H0001: External operation, External operation (JOG operation)
H0002: PU operation, External/PU combined operation, PUJOG operation
H0000: Network operation
H0001: External operation
H0002: PU operation
H0000 to HFFFF: Output frequency in 0.01 Hz increments
H0000 to HFFFF: Output current (hexadecimal)
Increments 0.01 A
H0000 to HFFFF: Output voltage (hexadecimal) in 0.1 V increments
H0000 to HFFFF: Monitor data selected in the instruction code HF3
Monitor selection data (Refer to
H0000 to HFFFF: Two latest fault records
b15
H74
H75
H76
H77
Fault record display example (instruction code H74)
With the read data H30A0
(Last fault : THT)
(Present fault : OPT)
b15
0
0 1 1 0 0 0 0
Last fault
(Refer to
page 210
for details on fault record read data.)
Control input commands such as the Forward rotation command (STF)
signal and the Reverse rotation command (STR) signal can be set. (For the
details, refer to
page
181.)
The states of the output signals such as the Forward rotation output,
Reverse rotation output, and Inverter running (RUN) signals can be
monitored. (For the details, refer to
Read the set frequency from the RAM or EEPROM.
H0000 to HFFFF: Set frequency in 0.01 Hz increments
Write the set frequency into the RAM or EEPROM.
H0000 to H9C40 (0 to 400.00 Hz): frequency in 0.01 Hz increments
To change the set frequency consecutively, write data to the inverter RAM.
(Instruction code: HED)
Data description
page 124
for details on selection No.)
b8 b7
Second fault in past
Latest fault
Fourth fault in past
Third fault in past
Sixth fault in past
Fifth fault in past
Eighth fault in past
Seventh fault in past
b8
b7
1
0 1 0 0 0 0 0
Present fault
(H30)
(HA0)
page
181.)
5.11 (N) Communication operation parameters
Number of data
digits
(format)
4 digits (B.E/D)
4 digits (A,C/D)
4 digits (B.E/D)
4 digits (B.E/D)
4 digits (B.E/D)
4 digits (B.E/D)
2 digits (B.E1/D)
2 digits (A1, C/D)
b0
4 digits (B.E/D)
b0
4 digits (A,C/D)
2 digits (A1, C/D)
4 digits (B.E/D)
2 digits (B.E1/D)
4 digits (B.E/D)
4 digits (A,C/D)
5. PARAMETERS
2
2
*1
3
4
5
6
7
8
9
10