Certification
• IEC 61850-3
General Requirements
• IEC 61000-6-2
Electromagnetic Compatibility (EMC) – Part 6-2: Generic Standards – Immunity for Industrial Environments
Section 6.2

EMC and Environmental Type Tests

The RSG2488 has passed the following EMC and environmental tests.
EMC Type Test for IEC 61850-3
NOTE
• In the case of an all fiber port configuration, this product meets all Class 2 requirements. Otherwise,
all Class 1 requirements are met for copper ports.
• If the unit contains copper ports, the IEC 1613 conformance is Class 1, during which disturbance
errors may occur but recovery is automatic.
• If the unit contains all fiber ports, the IEC1613 conformance is Class 2, during which no disturbance
errors will occur.
Test
IEC 61000-4-2
IEC 61000-4-3
IEC 61000-4-4
IEC 61000-4-5
IEC 61000-4-6
IEC 61000-4-8
44
Description
ESD
Radiated RFI
Burst (Fast Transient)
Surge
Induced (Conducted) RFI
Magnetic Field
Enclosure Contact
Enclosure Air
Enclosure Ports
Signal Ports
± 4 kV at 2.5 and 5 kHz
DC Power Ports
± 4 kV at 2.5 and 5 kHz
AC Power Ports
Earth Ground Ports
Signal Ports
± 4 kV Line-to-Earth
± 2 kV Line-to-Line
DC Power Ports
± 2 kV Line-to-Earth,
± 1 kV Line-to-Line
AC Power Ports
± 4 kV Line-to-Earth
± 2 kV Line-to-Line
Signal Ports
DC Power Ports
AC Power Ports
Earth Ground Ports
Enclosure Ports
100 A/m for 3 min
Test Levels
Severity Levels
± 8 kV
± 15 kV
20 V/m
± 4 kV at 5 kHz
10 V
1000 A/m for 3 s
EMC and Environmental Type Tests
RUGGEDCOM RSG2488