Remote mounting kit
Hide thumbs Also See for TrueSTEAM HM506:

Advertisement

Available languages

Available languages

Installation Guide
PRoPeR Hose installs
2 IN. PER FT
10 FT MAX
2 IN. PER FT
SUPPORTED REMOTE HOSE
NOTES:
• Minimum upward slope of hose in direction of steam flow is 2 in. per foot.
• Minimum downward slope of hose in direction of steam flow is 3/4 in. per foot.
• Maximum length of remote steam hose is 20 ft.
• Height of P-traps must be greater than the duct static pressure. (Typical 3 in.
will suffice.) P-trap must also be wetted.
• Minimize sharp bends and elbows.
AVOID THESE INSTALLATION MISTAKES.
NO SLOPE
KINKED
69-2276EFS—01
69-2276EFS_A.indd 4
20 FT MAX
WITH TRAP
P - TRAP
DRAIN
20 FT MAX
GENTLE BEND
2 IN. PER FT
OBSTRUCTION
DRAIN
SAG
5 FT MAX
IF NO SLOPE
IF NO SLOPE
2 IN. PER FT
TYPICAL INSTALLATION
DRAIN
DRAIN
WHEN TrueSTEAM IS ABOVE
REMOTE NOZZLE
WETTED P - TRAP
NOTE: HEIGHT OF TRAP MUST BE GREATER
THAN THE DUCT STATIC PRESSURE
NO SLOPE
4
P - TRAP
P - TRAP
UNDRAINED
ELBOW
M24915A
9/25/2008 9:26:42 AM