GND concept
Fig. 36: GND concept EKxxxx
Fuse protection
Coupler supply, fuse 1:
depending on the required current consumption and hence the configured terminals
typical max. 1 A
Power contacts, fuse 2:
permitted max. 10 A (slow-blow)
The coupler electronics and the power contacts can be supplied together from the same source. In this case
the fuse should be dimensioned for 10 A max.