Rinnai RV53E Operation And Installation Manual

Rinnai RV53E Operation And Installation Manual

Tankless water heater
Hide thumbs Also See for RV53E:
Table of Contents

Advertisement

Available languages

Available languages

RV53i
only
ANS Z21.10.3
CSA 4.3
INSTALLER: Leave this manual with the appliance.
CONSUMER: Retain this manual for future reference.
WARNING
result causing property damage, personal injury or death.
- Do not store or use gasoline or other flammable vapors and
liquids in the vicinity of this or any other appliance.
- WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electrical switch; do not use any phone in
your building.
Immediately call your gas supplier from a neighbor's phone.
Follow the gas supplier's instructions.
If you cannot reach your gas supplier, call the fire
department.
- Installation and service must be performed by a qualified
installer, service agency or the gas supplier.
Tankless Water Heater
Operation and Installation Manual
RV53i .................. REU-VB2020FFU-US
Table of Contents .............................................. 2
Consumer Safety Information ........................... 4
Operating Instructions ....................................... 5
Maintenance ..................................................... 9
Error Codes ..................................................... 10
Installation Instructions ................................... 14
Consumer Support .......................................... 39
French Version ................................................ 42
Register your product at www.rinnairegistration.com or call
1-866-RINNAI1 (746-6241)
If the information in these instructions is not
followed exactly, a fire or explosion may

Advertisement

Table of Contents
loading

Summary of Contents for Rinnai RV53E

  • Page 1: Table Of Contents

    CSA 4.3 Tankless Water Heater Operation and Installation Manual RV53i ... REU-VB2020FFU-US RV53e ... REU-VAM1620W-US Certified for installation in manufactured (mobile) homes. Table of Contents ... 2 Consumer Safety Information ... 4 Operating Instructions ... 5 Maintenance ...
  • Page 2: Table Of Contents

    Setting Controller to Mute ... 8 Setting the Clock ... 8 Maintenance Cleaning ... 9 Vent System (RV53i) ... 9 Air Intake and Exhaust (RV53e) ... 9 Motors ... 9 Temperature Controller ... 9 Lime / Scale Build-up ... 9 Snow Accumulation ... 9 Visual Inspection of Flame ...
  • Page 3: Rv53I

    (mobile) homes * Minimum flow may vary slightly depending on the temperature setting and the inlet water temperature. Rinnai is continually updating and improving products. Therefore, specifications are subject to change without prior notice. The maximum inlet gas pressure must not exceed the value specified by the manufacturer. The minimum value listed is for the purpose of input adjustment.
  • Page 4: Consumer Safety Information

    • Power Failure: The appliance will cut off the gas if it loses electrical power. The Rinnai water heater is one of the most advanced water heaters available. It provides a continuous supply of hot water at a preset temperature. This...
  • Page 5: Operating Instructions

    The RV53i and RV53e models do not come with a temperature controller. There are several models of temperature controllers that can be purchased separately. A maintenance display or status monitor is provided in the front panel to indicate operating status and error codes.
  • Page 6: Temperature Controller Settings

    Water temperatures over 125º F (52º C) can cause severe burns or scalding. Refer to the Danger Alert on water temperatures. Rinnai shall not, in any event, be liable for damages resulting from such misuse or misapplication.
  • Page 7: Using The Water Smart / Bath Fill Function

    2. Press the “Water Smart Bath Fill” button to set the water volume and temperature. 3. Press the “Temp” ▲ or ▼ buttons to obtain the desired temperature setting. RV53i & RV53e Operation and Installation Manual NOTICE Multiple Water Heaters NOTICE...
  • Page 8: Filling The Tub

    Press the “Function” button twice within 10 seconds to set the clock. Press the ▲ or ▼ button to reach the desired time. The clock on the BC-100V automatically shows the time which has been set on the MC-100V. RV53i & RV53e Operation and Installation Manual To stop the water flow during the Bath NOTICE Fill function, press the “Water Smart /...
  • Page 9: Maintenance

    Water Quality to see if your water needs to be treated or conditioned. (When checking maintenance code history, “00” is substituted for “LC”.) RV53i & RV53e Operation and Installation Manual Snow Accumulation Keep the area around flue terminal free of snow and ice.
  • Page 10: Error Codes

    The Rinnai water heater has the ability to check its own operation continuously. If a fault occurs, an error code will flash on the display in the front panel and on the temperature controller if installed. This assists with diagnosing the fault and may enable you to overcome a problem without a service call. Please identify the code displayed when inquiring about service.
  • Page 11 Nothing happens when code water flow is activated. RV53i & RV53e Operation and Installation Manual Remedy Check gas type of unit and ensure it matches gas type being used. Check for restrictions in air flow around unit and vent terminal.
  • Page 12: Trouble Shooting For Common Issues

    Off” button press the ▲ button. The last 9 error codes will flash one after the other. To exit this mode press the “On/Off” and ▲ button as before. To display the water flow through the water heater press and hold the ▲ button for 2 seconds and without releasing the ▲ button press the “On/Off” button.
  • Page 13: Flushing The Heat Exchanger (Error Code: Lc Or 00)

    O-rings. Cleaning solution is 4 gallons of undiluted virgin, food grade, white vinegar. RV53i & RV53e Operation and Installation Manual 3/4" Ball Valve 3/4" Union Check Valve Pressure Relief Valve Water Heater...
  • Page 14: Rv53I

    • The RV53i is not to be installed outdoors. • The RV53e is not to be installed indoors. • A qualified installer or service technician should install the appliance, inspect it, and leak test it before use.
  • Page 15: Clearances From Appliance

    Refer to the weight of the water heater in the Specifications section. NOTE: Rinnai water heaters should be installed in an upright position. Do not install upside down or on it side. RV53i & RV53e Operation and Installation Manual...
  • Page 16: Electrical Connection

    The wiring diagram is located on the Technical Sheet attached to the inside of the front cover. The water heater must be electrically grounded in accordance with local codes, or in the absence of local codes with the National Electrical Code, ANSI/NFPA 70 and/or the CSA C22.1, Canadian Electrical Code.
  • Page 17: Pipe Sizing Procedure - Example

    Capacity in cubic feet per hour Pipe Size (inches) Length RV53i & RV53e Operation and Installation Manual Gas Input of all gas products (BTU / HR) Heating Value of Gas (BTU / FT /HR. If the pipe length is 10 feet then the 3/4 inch /HR of natural gas.
  • Page 18: Water Piping

    8. Connect the OUTLET on the HOT water valve to the HOT WATER plumbing system. 9. Ensure that both drain valve lever handles are in the closed position (perpendicular to the drain portion of the body). RV53i & RV53e Operation and Installation Manual 107000081 107000083 107000085 107000086...
  • Page 19: General Instructions

    • Ensure that the water filter on the Rinnai water heater is clean and installed. • The relief valve should be added to the hot water outlet line and near the hot water outlet according to the manufacturer’s instructions.
  • Page 20: Freeze Protection Methods

    If the water heater is not going to be used during a period of possible freezing weather, it is recommended that the water inside the water heater be drained.
  • Page 21: Freeze Protection Piping

    In the event of a power failure at temperatures below freezing the water heater should be drained of all water to prevent freezing damage. The unit may be drained manually. However, Rinnai highly recommends that drain down solenoid valves be installed that will automatically drain the unit if power is lost.
  • Page 22: Error Indication Or Air Handler Control Switch (Rv53I)

    Error Indication or Air Handler Control Switch (RV53i) When using the Rinnai water heater with an Error Indication Switch, switch No. 4 in the bank of 8 switches should be in the off position. This is the default position. To connect the water heater to the Rinnai Air Handler, the Control Switch is necessary to function as the electrical connection.
  • Page 23: Recommended Piping For Circulation Systems

    Pump to be of bronze or stainless construction. IMPORTANT: Connect the building return line to the hot water supply line as close as possible to the Rinnai Water Heater. 3/4" Ball Valve 3/4" Union Check Valve Pressure Relief Valve...
  • Page 24: Venting Instructions (Rv53I) Intake / Exhaust Guidelines

    NOTICE If it becomes necessary to access an enclosed vent system for service or repairs, Rinnai is not responsible for any costs or difficulties in accessing the vent system. Warranty does not cover obtaining access to an enclosed vent system.
  • Page 25: Maximum Vent Length

    Corr/Guard Vent/Air Intake System Heat-Fab Telephone: 800-772-0739 Fax: 413-863-4803 E-mail: custsvc@heat-fab.com Web Site: www.heatfab.com RV53i & RV53e Operation and Installation Manual 17 ft 4 11 ft 4 5 ft 4 (5.2 m) (3.4 m) (1.5 m) Switch No. Notes 1234 Parts Metal-Fab Inc.
  • Page 26: Flue Installation - Concentric Venting (Rv53I)26

    Condensate Trap 3 in (75 mm) minimum Condensate Collector RV53i & RV53e Operation and Installation Manual * The condensate collector must be used in horizontal terminations if a vertical rise in the vent system exceeds 5ft. Maximum Height * 5 feet (1.52 m)
  • Page 27: Flue Terminal Clearances (Ans Z21.10.3, Csa 4.3 )

    For clearances not specified in ANSI Z223.1/NFPA 54 or CSA B149.1, clearances are in accordance with local installation codes and the requirements of the gas supplier. Clearance to opposite wall is 24 inches (60 cm) for Canada and US. RV53i & RV53e Operation and Installation Manual ANS Z21.10.3, CSA 4.3) INSIDE...
  • Page 28: Additional Clearances

    60" between Rinnai terminals (1.52 m) between 60" Rinnai terminals at different levels RV53i & RV53e Operation and Installation Manual RV53 (0.91 m) to ventilated or unventilated soffit or eve vent; or to a deck or porch (0.30 m) between...
  • Page 29: Connecting Multiple Water Heaters

    MSA-2S. The RV53e can use Rinnai pressure activation valves (PVA’s) can be used to manifold 2 to 5 Rinnai water heaters in order to produce a stable water temperature and allow the water heaters to run efficiently. Water heaters will turn on as necessary to meet the demand for hot water.
  • Page 30 Technicien d'entretien qualifié. WARNING 1. Turn off the power source and gas supply to the water heater / Coupez l`alimentation de gaz et électrique. 2. Remove the front cover from the water heater/ Enlever la couverture de devant du chauffe-eau.
  • Page 31: Temperature Controller Installation Location

    22 AWG. The maximum cable length from each controller to the water heater depends on the total number of wired controllers connected to the water heater. RV53i & RV53e Operation and Installation Manual • Avoid locations where the temperature controller could be splashed with liquids.
  • Page 32: Mounting The Controller (Rv53I)

    2. Make three holes in the wall as shown. 3. Run the cable between the controller and the Rinnai water heater or the controller and the other controller. 4. Remove the face plate from the temperature controller using a screwdriver.
  • Page 33: Mounting The Controller (Rv53E)

    1. Determine a suitable location for the controller. 2. Make three holes in the wall as shown. 3. Run the cable between the controller and the Rinnai water heater or the controller and another controller. 4. Remove the face plate from the temperature controller using a screwdriver.
  • Page 34: Operating Instructions

    ON/OFF button. 2. Set the thermostat to lowest setting. RV53i & RV53e Operation and Installation Manual If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
  • Page 35: Technical Data

    Pressure Drop Curve Outlet Flow Data RV53i & RV53e Operation and Installation Manual Technical Data Water Flow (gpm) RV53i RV53e delta T - Temperature Rise (ºF) RV53e RV53i...
  • Page 36: Space Heating

    Iron Components Do not use Rinnai water heaters directly for space heating applications involving iron radiators or applications with any iron components. Iron components may oxidize creating rust that will clog the inlet filter of the Rinnai water heater. RV53i & RV53e Operation and Installation Manual...
  • Page 37: Dimensions

    From base to hot connection * This is the minimum dimension from the wall. The wall bracket is adjustable to allow an additional 1.57 inches (40 mm). RV53i & RV53e Operation and Installation Manual GAS CONNECTION COLD WATER INLET RV53i in (mm) 13.8 (350)
  • Page 38: Ladder Diagrams

    Ladder Diagrams RV53i RV53e RV53i & RV53e Operation and Installation Manual...
  • Page 39: Consumer Support

    Limited Warranty What is covered? This Warranty covers any defects in materials or workmanship when the product is installed and operated according to Rinnai written installation instructions, subject to the terms within this Limited Warranty document. This Warranty applies only to products that are installed correctly.
  • Page 40 Replacement of the product may be authorized by Rinnai only. Rinnai does not authorize any person or company to assume for it any obligation or liability in connection with the replacement of the product. If Rinnai determines that repair of a product is not possible, Rinnai will replace the product with a comparable product at Rinnai’s discretion.
  • Page 41: State Regulations

    NOTICE BEFORE INSTALLATION Rinnai direct-vent appliance must be installed by a state qualified or licensed contractor and a properly trained Rinnai Installer. If you are not properly trained, you must not install this unit. IMPORTANT: In the State of Massachusetts (248 CMR 4.00 & 5.00)
  • Page 42: French Version

    Si vous ne pouvez rejoindre le fournisseur, appelez le service des — L'installation et l'entretien doivent être assurés par un installateur ou un service d'entretien qualifié ou par le fournisseur de gaz. Manuel d'installation et d’utilisation – RV53i & RV53e Instructions d'utilisation Comportements et pratiques de sécurité ... 43 Réglage de température ...
  • Page 43: Instructions D'utilisation

    à cette température sauf un changement désiré au point d’origine ou à n’importe quelle commande. Manuel d'installation et d’utilisation – RV53i & RV53e Instructions d'utilisation • Cet appareil est équipé d'une prise de trois-fourche pour votre protection contre le risque de choc et devrait être branché...
  • Page 44: Plages De Température Avec Un Contrôleur De Température

    à une température sûre. Arroser des températures plus de 125º F (52º C) peut causer des brûlures ou scalding sévère. Se référer à l'Alerte de Danger sur les températures d'eau. Rinnai ne fait pas, en tout cas, être responsable des dommages qui résultent de tel usage impropre ou tel mauvais usage.
  • Page 45: Entretien

    (Lors de la vérification de l'historique des anomalies pour l'entretien, le code « 00 » aura remplacé « LC ».) Manuel d'installation et d’utilisation – RV53i & RV53e Accumulation de neige Maintenez la zone autour de la terminaison de cheminée libre de toute neige et glace.
  • Page 46: Instructions D'installation

    • La RV53i ne doit pas être installé à l'extérieur. • La RV53e ne doit pas être installé à l'intérieur. • C'est un installateur ou un technicien de service qualifié qui doit installer, inspecter et vérifier l'absence de fuites de cet appareil avant sa mise en service.
  • Page 47: Écartements Par Rapport À L'appareil

    Reportez-vous au poids des modèles de chauffe-eau dans la section des spécifications. Remarque : Les chauffe-eau de Rinnai doit être installé dans une position verticale. N'installez pas à l'envers ou sur ce côté. Manuel d'installation et d’utilisation – RV53i & RV53e...
  • Page 48: Installation À Altitude Élevée

    Une vanne manuelle de coupure de gaz doit être placée sur la conduite d'alimentation en gaz en amont du chauffe -eau Rinnai. Un raccord union peut être utilisé sur la connexion au-dessus de la vanne de coupure pour pouvoir ultérieurement intervenir sur l'unité en la déconnectant.
  • Page 49: Tuyauterie D'eau

    CHAUDE du système de plomberie. Assurez-vous que les deux leviers de drainage soient en position fermée, (perpendiculaires à la portion drainage du corps). Manuel d'installation et d’utilisation – RV53i & RV53e 107000081 107000083 107000085 Valve de dégagement de pression (VDP)
  • Page 50: Qualité De L'eau

    être connecté à un appareil utilisé auparavant comme chauffage et fourniture d’eau non potable. • Le filtre d’eau du chauffage Rinnai dout être propre et installé. • La soupape de sûreté doit être actionnée manuellement au moins une fois par an pour vérifier qu'elle est toujours fonctionnelle.
  • Page 51: Tuyauterie Recommandée Pour Installation De Base

    Raccord union 3/4 po (19 mm) 3/4" Union Clapet anti-retour Check Valve Soupape de décharge Pressure Relief Valve Manuel d'installation et d’utilisation – RV53i & RV53e Rinnai Chauffe-eau Water Heater Rinnai Conduite d'alimentation en eau froide en 3/4 po (19 mm) Ceci n'est pas un schéma technique, son but n'est que de vous guider, et il ne tient...
  • Page 52: Instructions De Ventilation (Rv53I) Consignes Pour Aspiration/Évacuation

    AVIS S'il devient nécessaire d'accéder à un circuit de mise à l'air libre inclus pour le service ou les réparations, Rinnai n'est pas responsable d'aucuns coûts ou difficulté en accédant au circuit de mise à l'air libre. La garantie ne couvre pas obtenir l'accès à...
  • Page 53: Longueur Maximum De Ventilation

    Contacts avec les constructeurs de ventilation pour des informations d'installation et de liste de pièces : Rinnai/Ubbink Téléphone : 800-621-9419 Fax : 678-829-1666 Site Web : www.rinnai.us Manuel d'installation et d’utilisation – RV53i & RV53e Nombre de coudes à 90° 29 ft 3 23 ft 4 (8.8 m) (7.0 m)
  • Page 54: Espacements Pour Terminaison De Cheminée

    Pour les espacements non spécifiés dans ANSI Z223.1/NFPA 54 ou CSA B149.1, il faut appliquer les valeurs conformes aux normes locales d'installation et aux exigences du fournisseur de gaz.. L'espacement par rapport au mur opposé est de 24" (60 cm) pour Canada et USA. Manuel d'installation et d’utilisation – RV53i & RV53e DÉTAIL D'ANGLE INSIDE INTÉRIEUR...
  • Page 55: Installation De Conduit De Cheminée (Rv53I)

    3 in (75 mm) minimum Collecteur de condensat Manuel d'installation et d’utilisation – RV53i & RV53e * Un collecteur de condensat est requis sur les terminaisons horizontales si une élévation verticale dans le système de ventilation dépasse 5' (1.52 m).
  • Page 56: Instructions D'utilisation

    M/A. Réglez le thermostat sur la consigne la plus basse. Manuel d'installation et d’utilisation – RV53i & RV53e Si vous ne suivez pas exactement ces instructions, il peut en résulter un départ d'incendie ou une explosion, causant dégâts •...
  • Page 57: Diagramme En Escalier

    D'EAU 2 THERMISTANCE D'ÉCHA- CIRCUIT DE GEUR THERMIQUE THERMIS- TANCE THERMISTANCE DE BRÛLEUR THERMISTANCE DE TEMPÉRATURE D'AIR Manuel d'installation et d’utilisation – RV53i & RV53e NEUTRE FUSIBLE 3 A ANTI-FOUDRE ANTI-FOUDRE VARISTOR TERRE ALLUMAGE 12 V CC 40 V CC DÉTECTEUR...
  • Page 58: Support À La Clientele

    Cette garantie couvre tous défauts dus aux matériaux et à la main d'œuvre quand le produit a été installé et utilisé en suivant les instructions écrites d'installation de Rinnai, dans les termes décrits dans ce document de garantie limitée. Cette garantie s'applique seulement aux produits qui sont installés correctement.
  • Page 59: Garantie Limitée

    Rinnai le remplacera par un produit comparable, à sa discrétion. Si un composant ou un produit retourné à Rinnai est trouvé sans défaut du aux matériaux ou à la main d'œuvre, ou qu'il est déterminé qu'il a été...
  • Page 60 060 00012 31348 2 (VAM1620W, VB2020FFU) U287-1821X01(00) © 2010 Rinnai America Corporation Printed in Japan...