Table of Contents

Advertisement

3-2 Installation interval

● Interference prevention function is not incorporated in this product. In case mounting two
sets of this product close together, please mount it as drawing below indicates. (Typical
example)
● Find out the operating point ℓ1 on the parallel deviation diagram for the sensing distance
L1. Separate sensors by 2 X ℓ1 or more.
EX-Z11□, EX-Z11F□
<Parallel deviation diagram (typical)>
80
60
40
20
0
20
10
Left
Operation distance ℓ(mm)
<Installation interval>
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
(L1)
(ℓ1)
0
10
20
Center
Right
50mm
In case using at sensing distance (L1) 50mm, the
operation point (ℓ1) is approx. 8.02mm according
to diagram above.
The installation interval is
Approx. 8.02mm X 2 = approx. 16.04mm
Thus, install the product to approx. 16.04mm or
more away.
16.04mm
16.04mm