Table 5. Setpoint values vs. resistances (Celsius)
setpoint
nom. res.
rel./K
(Ω)
-5
9574.0
-4
8759.2
-3
7944.4
-2
7129.6
-1
6314.8
0
5500.0
1
4685.2
2
3870.4
3
3055.6
4
2240.8
5
1426.0
Table 6. Setpoint values vs. resistances (Fahrenheit)
setpoint
nom. res.
rel./K
(Ω)
-10
10026.7
-9
9574.0
-8
9121.3
-7
8668.7
-6
8263.7
-5
7763.3
-4
7310.7
-3
6858.0
-2
6405.3
-1
5952.7
0
5500.0
1
5047.3
2
4594.7
3
4142.0
4
3689.3
5
3236.7
6
2784.0
7
2331.3
8
1878.7
9
1426.0
10
973.3
setpoint
nom. res.
abs./°C
(Ω)
12
9958.0
13
9468.7
14
8979.3
15
8490.0
16
8000.7
17
7511.3
18
7022.0
19
6532.7
20
6043.3
21
5554.0
22
5064.7
23
4575.3
24
4086.0
25
3596.7
26
3107.3
27
2618.0
28
2128.7
29
1639.3
30
1150.0
setpoint
nom. res.
abs./°C
(Ω)
55
9577.4
57
9033.7
59
8490.0
61
7946.3
63
7402.6
65
6858.9
67
6315.2
69
5771.5
70
5499.6
71
5227.8
73
4684.1
75
4140.4
77
3596.7
79
3053.0
81
2509.3
83
1965.6
85
1421.9
T7560A,B,C DIGITAL WALL MODULES
Field Wiring
16 to 22 AWG (1.5 to 0.34 mm
application.
2
18 AWG (1.0 mm
Max. length of wire from a device to a wall module is
164 ft (50 m).
Twisted pair wire recommended for wire runs longer
than 100 ft (30.5 m).
Setpoint Adjustment Range (A and B)
Setpoint can be configured for
Fahrenheit absolute (55 ... 85 °F)
Fahrenheit relative ( ± 10)
Celsius absolute (12 ... 30 °C)
Celsius relative ( ± 5)
Temperature Value Display Resolution (A and B)
Degree Celsius ⇒ 0.1 °C
Degree Fahrenheit ⇒ 0.1 °F
Setpoint Value Display Resolution (A and B)
Degree Celsius ⇒ 0.5 °C
Degree Fahrenheit ⇒ 1.0 °F

Mounting Options

Wall mounting
Dimensions(H/W/D)
4-1/8 x 3-15/16 x 1-3/16 in. (104 x 99 x 30 mm)

Environmental Ratings

Shipping temperature: -22 ... +140 °F (-30 ... 60 °C)
Operating temperature: 32 ... 104 °F (0 ... +40 °C)
Relative humidity: 5% to 95% non-condensing
Measurement range: +6 ... +40 °C
Approval Bodies
UL 916, NEC Class 2
CE
3
) depending on
2
) min. for 24 Vac power wiring.