FCC ID: M5ZANA

Example:

C1283FA60B000000EC000F8AD0AB<CR>
C1283FA60B000000EC000F8AD0AB <CR>
C1283FA60B000000EC000F8AD0AB <CR>
C1283FA60B000000EC000F8AD0AB <CR>
C1283FA60B000000EC000F8AD0AB <CR>
C828AE9105000000AA2D2DD474AB <CR>
This field is the mode indicator, the LS-bit which indicates the
service state of the transmitter, C1=normal, C0=service mode.
This field is the unique serial number of the 1-Wire sensor.
This is analog data field stored MSByte first as a 12-bit number in
a 16-bit field. The number shown is 000F (15) or 15/4096 of full
scale. If this is a 0-20 milliamp input this would be .07 MilliAmp.
If the input is 0-5 Volts this would be 0.0183 Volts.
This field is the CRC-16 error check as was originally received and
checked. This CRC is over the first 11 bytes of the packet starting
with the mode flags and ending with inclusion of the temperature
data.
This field is the mod 256 sum of all the ASCII character values in
the response but does not include the <CR>.
This is the CR terminator, 0Dhex.