9.2 Configuration

9.2.1 Setting Communication Conditions

 Configuration
Setting items
Communication
mode
Station no.
Baud rate
Data length
Parity
Stop bit
RS/CS
Send waiting
time
(unit: 0.01 ms)
Start code STX
Terminator
setting
Terminator
judgment time
(unit: 0.01 ms)
Modem
initialization
(Note 1) In general-purpose communication, the following setting items need not to be specified.
Station no., PLC link
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Default
Specification range
General-purpose
MEWTOCOL-COM
communication
1
1 - 999
300 / 600 / 1200 / 2400
/ 4800 / 9600 / 19200 /
9600
38400 / 57600 / 115200
/ 230400
8 bits
7 bit / 8 bits
Odd
None / Odd / Even
1 bit
1 bit / 2 bits
Invalid
Invalid / Valid
0
0 - 10000
Invalid
Invalid / Valid
CR / CR+LF / Time /
CR
ETX
0 - 10000
0
(0 - 100 ms)
Do not initialize /
Initialize while
Do not initialize
performing settings /
Re-initialize while
performing settings
9.2 Configuration
Remark
Specify "general-purpose
communication".
Settings are not necessary.
The setting must be done according to
the devices connected.
Set to "Valid" only when Communication
Cassette AFP7CCS2 is used in a 5-wire
mode.
Set this when it is necessary to delay
response to the partner device.
The setting must be done according to
the devices connected.
In cases where "Time" is specified in the
terminator setting, set the time for judging
the terminator.
Perform settings only when a modem is
to be connected. Perform settings for
start-up modem initialization.
9-3