11.4.2 MODBUS RTU Response Format

 Response in normal status
 The same message as a command is returned and for a loop back test.
 A part of a command message (6 bytes from the beginning) is returned for multiple write
command.
 Response in abnormal status
In case a parameter disabled to be processed is found in a command (except transmission
error)
Slave address (station no.)
Function code + 80H
Error code
CRC
 Error code contents
1. Function code abnormality
2. Device No. abnormality (out of range)
3. No. of devices abnormality (out of range)
11-14
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Either 1, 2 or 3