Executing Machining Programs
if applicable, the machining program error number and
if applicable, the number of the statement in which the error was recognized.
Following this, the machining program is output in ASCII characters.
4.3.22

Enter SYSID (Mode 24)

With mode 24 (SYSI D input), a module identifier (SYSID) is entered on the I P247. This is neces-
sary when a module has been exchanged before you transfer machine data.
When operating the I P247 using C0M247, the SYSID input does not appear directly. It is trig-
gered when you press <Fl> (begin) in the presets display (=> Section 5.4 "Start COM247").
The data entered and displayed in the presets display is then written to the module.
From the PC side you can execute this mode with FBI 65 via the data channel.
The module identifier consists of the following elements:
Module type:
The type consists of the characters "IP247". The module type cannot be changed.
Version:
This indicates the firmware version. For example, A02.1 for firmware version 2,1. It consists of
five characters and cannot be changed.
Module number:
This is a number between O and 99 which you assign to differentiate between positioning mod-
ules. The same number must also be entered in the machine data of the three axes.
Note
The module number can no longer be changed once a correct machine data re-
cord (MD) exists on the module. If you attempt to change this number, the error
"correct MD - module number cannot be changed" is output.
Slot number:
This number can be selected between O and 255. It is only used for documentation
4-42