Owners &
Installation
LISTINGS AND CODE APPROVALS
These gas appliances have been tested in
accordance with AS4553-2000, NZS 5262
and have been certifi ed by the Australian
Gas Association for installation and opera-
tion as described in these Installation and
Operating Instructions.
Your unit should be serviced annually by
an authorised service person.
IG35 Gas Inbuilt
PLEASE KEEP THESE INSTRUCTIONS
FOR FUTURE REFERENCE
WARNING:
Improper installation, adjustment, altera-
tion, service or maintenance can cause
injury or property damage. Refer to this
manual. For assistance or additional in-
formation consult an authorised installer,
service agency or the gas supplier.
FOR YOUR SAFETY
Do not store or use gasoline or other fl am-
mable vapours and liquids in the vicinity of
this or any other appliance.
Installation and service must be performed
by an authorised installer, service agency or
the gas supplier.
918-448b
Models:
IG35-NG
IG35-LPG
IG35-ULPG
FOR YOUR SAFETY
What to do if you smell gas:
Do not try to light any appli-
ance
Do not touch any electri-
cal switch: do not use any
phone in your building.
Immediately call your gas
supplier from a neighbour's
phone. Follow the gas sup-
plier's instructions.
If you cannot reach your
gas supplier, call the fi re
department.
06/23/08

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the IG35-NG and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Regency IG35-NG

  • Page 1 Installation and service must be performed by an authorised installer, service agency or the gas supplier. 918-448b Models: IG35-NG IG35-LPG IG35-ULPG FOR YOUR SAFETY What to do if you smell gas: Do not try to light any appli-...
  • Page 2: Unit Dimensions

    GAS INBUILT FIREPLACE TO THE NEW OWNER Congratulations! You are the owner of a state-of-the-art Gas Inbuilt Fireplace by FPI. The Regency Gas Fireplace Series of appliances has been designed to provide you with all the warmth and charm of a fi replace, at the fl ick of a switch. The model IG35 of this series has been approved by Australian Gas Association for both safety and effi...
  • Page 3: Table Of Contents

    Faceplate, Trim & Louver Installation ...15 Premium Flush Front Installation ...16 Remote Control ...21 Final Check...21 Standard Wiring ...21 Wiring with Premium Flush Front Option ...22 Regency IG35 Gas Inbuilt Fireplace TABLE OF CONTENTS OPERATING INSTRUCTIONS Operating Instructions ...23 Lighting Instructions...23 Shutdown Instructions ...23 First Fire ...23...
  • Page 4: Data Badge

    DATA BADGE This is a copy of the label that accompanies each Regency IG35 Gas Inbuilt fi replace. We have printed a copy of the contents here for your review. DATA BADGE NOTE: Regency units are con- stantly being improved. Check the label on the unit and if there is a difference, the label on the unit is the correct one.
  • Page 5: Installation

    fi replace re-approved by the authority having jurisdiction." INSTALLATION INSTALLATION CHECKLIST The Regency Gas Insert is installed as listed below. 1) Unit Location - refer to "Clearances to Combustibles" section. 2) Make the gas connections. Refer to "Gas Connections"...
  • Page 6: Minimum Fireplace Dimensions

    INSTALLATION MINIMUM FIREPLACE DIMENSIONS The minimum fi replace dimensions for the Regency gas space heater are shown in the following diagrams: Premium Flush Front Framing When installing the Premium Flush Front, the walls surrounding the zero clearance kit must be made of non-combustible material. See Diagram below.
  • Page 7: Flueing

    fl ue liner running the full length of the chimney. A minimum fl ue height of 1.5 m. is recommended. The Regency Inbuilt Fireplace incorporates its own internal draft diverter, so no additional external draft diverter is required.
  • Page 8: Aeration Settings

    INSTALLATION System Data IG35 IG35-NG: For 0 to 610 meters altitude IG35-LPG: For 0 to 610 meters altitude IG35-ULPG: For 0 to 610 meters altitude Burner Inlet Orifi ce Sizes: ULPG Burner Max. Input 33.5 mj 34 mj ULPG 28 mj Min.
  • Page 9: Conversion Kit #486-968 For Ng To Lpg

    5) Remove the grate. 6) Remove the burner and adjust the aeration setting to 15 mm fully open. Regency IG35 Gas Inbuilt Fireplace 7) Remove burner orifi ce with a 1/2" wrench and discard. Use a wrench to hold on to the elbow behind the orifi...
  • Page 10 19) Check operation of fl ame control. 20) Check for proper fl ame appearance and glow on logs. Installer Notice: These instructions must be left with the appliance. Regency IG35 Gas Inbuilt Fireplace...
  • Page 11: Conversion Kit #486-967 For Ng To Ulpg

    5) Remove the grate. 6) Remove the burner and adjust the aeration setting to 15 mm fully open. Regency IG35 Gas Inbuilt Fireplace 7) Remove burner orifi ce with a 1/2" wrench and discard. Use a wrench to hold on to the elbow behind the orifi...
  • Page 12 19) Check operation of fl ame control. 20) Check for proper fl ame appearance and glow on logs. Installer Notice: These instructions must be left with the appliance. Regency IG35 Gas Inbuilt Fireplace...
  • Page 13: Log Set Installation

    2) Sprinkle the embers on the front, left and right sides of the fi rebox base. Embers Embers Regency IG35 Gas Inbuilt Fireplace 3) Place Rear Log A)02-65 on the two pins on the rear log support. A)02-65 4) Place the Middle Left Log B)02-56 on the two pins from the rear left side.
  • Page 14 5) Test fi re to ensure proper light off. Ensure fl ame fl ows smoothly from one end of the burner to the other. If there is any fl ame hesitation, check the area for any blockage of the burner port. Regency IG35 Gas Inbuilt Fireplace...
  • Page 15: Faceplate, Trim & Louver Installation

    fi replace body using 4 black screws. Side Screws INSTALLATION 10) Push the Regency logo plate into the two holes in the bottom left corner of the face- plate. 11) Place the 2 hinges for the bottom louver in position and secure using 4 screws per hinge.
  • Page 16: Premium Flush Front Installation

    Then place the grommet over the sleeve and tuck into the hole in the heat shield as shown in diagram 5. Bolts CAT5 Cable Receptacle Washer Diagram 3 ECS Manual Switch Diagram 4 Grommet Diagram 5 Regency IG35 Gas Inbuilt Fireplace...
  • Page 17 See diagram 8. CAT5 Cable Diagram 8 Regency IG35 Gas Inbuilt Fireplace 12) Partially mount the heat shield to the left side of the faceplace and connect the CAT5 cable to the ECS manual control switch. See diagram 9.
  • Page 18 17) Remove the wire harness from the valve. See diagram 15. 18) Undo the wire clip to the right side of the valve. See diagram 16. Diagram 14 Valve Wire Harness Diagram 15 Diagram 16 Regency IG35 Gas Inbuilt Fireplace...
  • Page 19 See diagram 19. Diagram 18 Diagram 19 Regency IG35 Gas Inbuilt Fireplace 22) Connect the other end of the new wire harness to the valve, in place of the one removed in step 16. See diagram 20.
  • Page 20 Hinge 31) Plug in the power source. NOTE: The fan should run at least on low speed to prevent the unit from overheating which will cause automatic shutdown via the thermodisc safety switch. Diagram 26 Regency IG35 Gas Inbuilt Fireplace...
  • Page 21: Remote Control

    REMOTE CONTROL Use the Regency Remote Control Kit approved for this unit. Use of other systems may void your warranty. The remote control kit comes with a hand held transmitter and a wall mounting plate. 1) Choose a convenient location to mount the hand held transmitter, protection from extreme heat is very important.
  • Page 22: Regency Ig35 Gas Inbuilt Fireplace

    (grounding) plug for your and dangerous operation. protection against shock hazard and should be plugged directly into a prop- erly grounded three-prong receptacle. Do not cut or remove the grounding prong from this plug. Regency IG35 Gas Inbuilt Fireplace...
  • Page 23: Operating Instructions

    2) The LED will fl ash. 3) Turn off all electric power to the appliance if service is to be performed. Regency IG35 Gas Inbuilt Fireplace OPERATING INSTRUCTIONS FIRST FIRE The FIRST FIRE in your heater is part of the paint curing process.
  • Page 24: Copy Of Lighting Instruction Plate

    Blower: Regency gas appliances use high tech blowers to push heated air farther into the room. It is not unusual for the fan to make a "whirring" sound when ON.
  • Page 25: Maintenance Instructions

    MAINTENANCE DOOR GLASS REPLACEMENT Your Regency stove is supplied with high tem- perature, 5 mm Neoceram ceramic glass that will withstand the highest heat that your unit will produce. In the event that you break your glass...
  • Page 26: Fan Maintenance

    10) Pull out the fan tray. 11) Remove the 3 screws from the back of the fan tray to remove the fan. 12) Reverse the above steps to install the new fan. Regency IG35 Gas Inbuilt Fireplace Fan Ground Connectors Cable...
  • Page 27: Removing

    Glass Door Holder 12) Remove the fi rebox base plate by removing 11 screws which hold it in place. Regency IG35 Gas Inbuilt Fireplace 13) Remove the valve cover plate by removing the 3 screws. Valve Cover 14) Remove all the wire connectors from the valve and spark ignitor.
  • Page 28: Parts List

    The Control Box Cable wires for the IG35 come separately: 910-530, 910-504, 910-528 910-936 910-088 910-080 910-521, 910-522, 910-523, 910-525 FG37 FG38 FG39 N/A* 910-082 910-089 910-912 910-906 910-083 910-514 910-916 PG33 PG36 HG35 PG121/PG131 PG36D Regency IG35 Gas Inbuilt Fireplace IG35 N/A*...
  • Page 29: Main Assembly

    Burner Assembly - NG/LPG 63) 910-034 Pilot Assy (NG) - 3 fl ame convertible top 910-035 Pilot Assy (LPG) - 3 fl ame convertible top Regency IG35 Gas Inbuilt Fireplace MAIN ASSEMBLY Part # Description 7) 486-910 Flush Louvre set - Black (Top & Bottom)
  • Page 30: Faceplate Assembly

    *Not available as a replacement part. FACEPLATE ASSEMBLY Part # 176) 486-926 Hearth Trim 2" - Regular 180) 486-928 Hearth Trim 4" - Regular 181) 486-929 Flush Screen Door *Not available as a replacement part. Description Regency IG35 Gas Inbuilt Fireplace...
  • Page 31: Warranty

    fi ring as per rating plate. Any part or parts of this unit which in our judgement show evidence of such defect will be repaired or replaced at Regency through an accredited distributor or agent provided that the defective part be returned to the distributor or agent Transportation Prepaid, if requested.