Diagnostics
3.6.2 Building Management Systems
The Networked Wallmount WattStation will communicate to building management systems (BMS)
via Modbus over the CAT5 connection or WiFi. The EVSE comes with a Modbus register map that
the BMS integrator can integrate into their SCADA or server system(s).
Note: Static IP addressing should be used for the WattStation(s) and all Modbus clients.
3.6.3 Firmware Updates
The firmware for the EVSE will be upgradeable over the EVSE's TCP/IP interface (CAT5 or wirelessly
through the cellular router or WiFi Access Point). The firmware updates will allow GE to supply
customers with updated firmware that adds additional features to flexible charging algorithms,
ground fault detection performance, pricing models, communication protocols and other
performance enhancements. All firmware updates will be accessed and controlled through the GE
WattStation Connect.

3.7 Technical Details

SAE Compliant
Vehicle Interface
Cable Length
AC Max Charging Power Output**
Voltage and Rated current
AC Power Input
Short Circuit Rating
Recommended Service Panel Breaker
Ground Fault Protection
Cold Load Start
Local Area Network
Network Communication Protocol
Network Security
Cellular Router (Optional)
WiFi (Optional)
Metering Accuracy
RFID Reader
Display
Standby Power
© GE All Rights Reserved
-
Override of charging
-
Charging delay
-
Ground fault
-
Loss communication
-
RFID failure
-
Un-authorized users
-
Contactor monitor
-
Overload
-
Over/Under voltage
-
Invalid payment
Level II per J1772
SAE J1772 EV connector
25' cable
7.2 kW (240VAC @ 30A)
208-240VAC @ 30A
208-240VAC requiring only Line 1 and Line 2, or Line and Neutral, and
Earth ground
5kA @ 240 VAC
2-pole 40A breaker on dedicated circuit
Internal 20mA CCID with auto-re-closure, does not require a GFCI in
service panel
Random start up between 0 and 5 minutes
IEEE 802.3 ("Ethernet") compliant: 10BASE-T, 100BASE-TX
TCP/IP
GE recommends that network be VPN and Firewall protected
EV-DO / HSPA
IEEE 802.11b/g compatible with Antenna
< +/-2% accurate for all values (Current, Voltage, Power & Energy)
HID MultiClass RP15
LED Icons
10W typical