Service Manual
Compact 3010

Advertisement

loading

Summary of Contents for Alde Compact 3010

  • Page 1 Service Manual Compact 3010...
  • Page 2: Table Of Contents

    CONTENTS Page Chap Designation Page Chap Designation About the Alde central heating system Replacing spark electrode Maintaining the heating system Replacing flame sensor About the Compact 3010 Replacing solenoid valve How the heater works Replacing sensor The LPG boiler Fault messages in the panel...
  • Page 3: Maintaining The Heating System

    To make refilling and bleeding easier, we recommend using source. The electrical elements, of which there are two, have the Alde filling pump which quickly both fills and bleeds the an output of 1kW and 2kW respectively. The output is control- system automatically.
  • Page 4: The Lpg Boiler

    THE LPG BOILER Warm water Starting The heater continuously keeps warm water at a basic tem- perature of about 50ºC. If the temperature goes down below When the gas heater receives the signal to start, the system this level, the heater increases power to a level in accordance commences with an auto-check period in which the fan starts with the control steps above.
  • Page 5: Replacing Components

    Always switch off the 12 V DC and 230 V ~ power supply, and turn the main gas cock to the off position before starting any servicing. The seals (marked in red) must NOT be broken unless special permission has been obtai- ned from Alde. REPLACING THE PRINTED CIRCUIT...
  • Page 6: Replacing A Burner

    REPLACING A BURNER REPLACING SPARK ELECTRODE 1. Remove the service panel on the boiler. When replacing the spark electrode, also replace the . Release the fan in accordance with 3:2. flame sensor. . Remove the sensor cable (fig. 4A) and spark electrode 1.
  • Page 7 REPLACING THE SOLENOID VALVE REPLACING THE SENSOR 1. Remove the service panel on the boiler. 1. Remove the service panel on the boiler. . Release the connection block (fig. 1J) from the printed . Release the 6-point connection block (fig. 10A) from circuit board.
  • Page 8: Fault Messages In The Panel

    FAULT MESSAGES IN THE PANEL WINDO Caused by: NB! Fault messages are only shown when the panel is idle Connection no. 4 in the panel’s accessory block is broken. GAS OUT is reset by the main breaker being switched off When this is broken, the heater does not function with LPG.
  • Page 9: Exploded Diagram

    EXPLODED DIAGRAM...
  • Page 10: Article Numbers On Exploded Diagram

    ARTICLE NUMBERS ON EXPLODED DIAGRAM (FOR SPARE PARTS, SEE PAGE 1) 1. 010 19 Service cover 21. 010 1 Spark electrode 2. 010 18 Service panel 22. 010 18 Nut 3. 010 1 Cover 23. 010 181 Screw 4. 010 0 Printed circuit board 2 kW 24.
  • Page 11 WIRING DIAGRAM WITH CONTROL PANEL...
  • Page 12: Spare Parts

    SPARE PARTS 1. 000  Fan compl. 1. 010 01 Burner compl. 2. 010 0 Solenoid valve compl. 1. 010 0 Printed circuit board, 2kW 1. 010 0 Sensor set compl. 2. 010 0 Printed circuit board, 3kW 2. 010 0 Spark electrode/Flame sensor...