Data transfer using CANopen
Abort Name
SDO protocol time
overflow
Illegal access
Illegal access
Object not available in the
object directory
General parameter
incompatibility
Data type does not match
the length of the SDO
value, SDO value too
high or too low
Subindex does not exist
Parameter value
exceeded
General error
Data transfer error
Data not able to be
transferred or saved due
to local control
Service error
Working with the SDO<->parameter channel
The CANopen option module offers an SDO->parameter channel, which can be
used to read or write all parameters (PKW objects) of the MICROMASTER
420/430/440. In this case, it does not involve CANopen objects in the true sense.
The reason for this is that the numbering of the sub-indices with respect to CAN-
open differs (subindex 0 does not contain the number of objects, but already the
first object). However, the objects from the parameter channel can be read and
written just like CANopen objects using SDO access operations. Their object
number must be appropriately converted. They are designated by a * in this
document.
40
Abort Code
Description
05040000H
MICROMASTER had not responded within xxxs to a parameter task of
the option module.
The CANopen module cancels the request.
06010001H
This parameter can only be write accessed (write only)
(parameter value cannot be read)
06010002H
Parameter is a read-only parameter
(parameter value cannot be changed)
06020000H
Access to a non-existing object
(parameter number does not exist)
06040043H
Illegal parameter value
(the parameter only permits specific values)
06070010H
Mixture between word and double word
(incorrect data type)
06090011H
SDO access to a non-existing subindex of an object
(erroneous subindex, no array)
For tasks from "indexed parameter to non-indexed parameter" type
Example: Task: 'Change parameter value (word, array)' for non-indexed
parameters
06090030H
Upper or lower limit value exceeded (write only)
08000000H
Incorrect parameter status:
Parameter, read or write buffer simultaneously used in both directions
New parameter task is sent before the previous has been responded to.
08000020H
Data cannot be transferred to the application or cannot be saved.
08000021H
Change request without having status as higher-level control (refer
to P0927, corresponds to object 0x239F*)
Drive converter parameter: 'Access code' and/or 'Special parameter
access' presently not set
(the operator has no change authorization
for the PKW interface)
08000022H
The drive converter does not permit the presently output task
(the task cannot be executed due to the operating state)