ZONES
Control data and settings for individual zones can be viewed
and modified using the RapidZone command display. A
typical screen is displayed below.
TO CHANGE TEMPERATURE SETPOINTS
Starting at the Main screen, make the following selections to
select the specific zone whose setpoint you want to change.
Main—>BuildngVw—>Zone Data—>Zone Name
Room Temp
Control Setting
Occupancy Status
Operating Mode
Damper Pos
Press ChngValue to view and modify setpoints.
Highlight Details and press the down arrow key to
display the setpoint screen below. Use + or - and
press Apply to change the temperature setpoint.
Occupied
Standby
Unoccupied
NOTE: Standby setpoints must always be set equal to the
unoccupied temperature setpoint.
Press the Back key to return to the first Zone Name
screen.
Press OccOvride to display the override screen where
you can set timed or continuous Occupied or Unoccupied
override.
NOTES:
74-3450—2
Zone Name
Zone Name
Heat
70.0 DF
62.0 DF
62.0 DF
The Occupied setpoint defines the comfort level
desired during periods when a given area or zone
is in use. The Unoccupied setpoint captures
operational, equipment and energy savings
during periods when a given area or zone is not
in use.
In zones with temperature sensor and setpoint
adjustment, the occupied temperature setpoint is
controlled by the zone sensor. The command
display should not be used to modify the
occupied setpoints for these zones.
Be sure to press the Apply key after you've made
any changes that you want saved.
71.3 F
76.5 F
Occupied
Cool
60%
Cool
74.0 DF
82.0 DF
82.0 DF
2
!!
Next
Prev
ChngValue
OccOvride
M18306
!!
+
-
Apply
OccOvride
Cancel
M18585