Download Print this page
Raypak XFYRE 300-850 Specifications

Raypak XFYRE 300-850 Specifications

Type h condensing heating boilers

Advertisement

Quick Links

Job:
Engineer:
Contractor:
Prepared By:
Model:
Up to 94% Thermal Efficiency at Full Rate
100% Factory Fire Tested
Maximum Outlet Water Temperature: 210°F
Maximum System Temperature: 200°F
Full Safety Diagnostics with History
Footprint: Less Than 9-1/2 ft
Limited Twenty-Year Thermal Shock Warranty
Limited Ten-Year Heat Exchanger Warranty
Full Electronic Modulation, Constant Ratio 5:1 Turndown
Soft-Start Modulating Controller with LCD Display
Status and Full Diagnostics Display
Heat Exchanger
All Stainless Steel Construction
Gasketless Heat Exchanger Design
ASME H Stamped
160 PSIG Working Pressure
National Board Approved
ASME Pressure Relief Valve
60 PSIG – Standard
PSIG – Optional
Temperature and Pressure Gauge,
Shipped Loose
Control
120V, 60Hz, 1Ø, Power Supply
Digital Operating Control with LCD
display.
Outdoor reset with Indirect Priority
0-10 VDC input for BMS
Cascade up to 8 boilers
Spark Ignition (IID)
Remote Flame Sensor
High Limit, Manual Reset, Fixed,
200ºF
Auto Limit, Fixed, 210ºF
Alarm Dry Contact Connection
On/Off Power Switch
Flow Switch
Blocked Vent Pressure Switch
Boiler, DHW & System Pump
Contacts
Water Temperature Sensors (3)
Burner
Ultra-Low NOx: Less than 20 PPM
Catalog No.: 2000.17
Date:
Indoor/Outdoor:
2
Gas Train
Fuel
Natural Gas
Propane
Zero Governor Regulator
Dual-Seat Combination Valve
Electronic Modulating Firing Mode (H7)
Construction
Indoor/Outdoor Construction
Front Controls Enclosed
PolyTuf Powder Coat Finish
Rear Connections (Electrical, Gas, Vent,
Combustion Air)
Top Connections (Water)
Design Certified ANSI Z21.13/
CSA 4.9
Venting (PVC-CPVC-Stainless.)
Vent Termination
Indoor, Vertical – Option D-11
Indoor, Horizontal – Option D-15
Outdoor
Extractor - Optional
By others
Not required
Effective: 6-22-09
Replaces: New
XFyre™ - Type H
Condensing Heating Boilers
Models 300-850
Multi-Boiler System Controllers
B-36 TempTracker Mod+ Digital
Controller, 2-4 Boilers, OA Reset
B-37 TempTracker Mod+ Digital
Controller, 5-10 Boilers, OA Reset
B-38 TempTracker Mod+ Digital
Controller, 11-16 Boilers, OA Reset
Options
D-21 TruSeal™ Combustion Air Inlet
P-
Pump:
HP, 120V, 1∅, 60Hz
Cast Iron
S-1
Low Gas Pressure Switch,
Manual Reset
S-2
High Gas Pressure Switch,
Manual Reset
Z-12 Condensate Neutralizer Kit
Regulatory Agency Requirements
Bronze

Advertisement

loading

Summary of Contents for Raypak XFYRE 300-850

  • Page 1 200ºF Auto Limit, Fixed, 210ºF Alarm Dry Contact Connection On/Off Power Switch Flow Switch Blocked Vent Pressure Switch Boiler, DHW & System Pump Contacts Water Temperature Sensors (3) Burner Ultra-Low NOx: Less than 20 PPM Catalog No.: 2000.17 Effective: 6-22-09...
  • Page 2 XFyre – Type H Models 300-850 MBTUH Model (H7-) Length Input Output 28-1/4 37-1/4 54-1/4 Ratings shown are for elevations up to 2,000 feet. For installations at elevations above 2,000 feet, please consult the factory for additional instructions. 20ºF ∆T Model ∆P (H7-)

This manual is also suitable for:

Xfyre 300Xfyre 500Xfyre 850