Download Print this page

Toshiba tosvert VF-AS3 Instruction Manual page 8

Hide thumbs Also See for tosvert VF-AS3:

Advertisement

H 1 or more
11 cm
or more
H 2 or more
Type
VFAS3-2004P - 2370P
VFAS3-4004PC - 4750PC
VFAS3-2450P, 2550P
VFAS3-4900PC - 4132KPC
VFAS3-4160KPC
VFAS3-4200KPC - 4280KPC
1) Basic installation
When installing multiple inverters, leave at least 11 cm or more of space between each inverter and install them
aligned horizontally.
When using the inverter in locations with temperatures above 50°C, remove the top cover and operation panel of the
inverter (refer to [2. 2] of instruction manual (E6582062)) and use the inverter with the output current reduced (refer
to [3]).
2) Side-by-side installation
To align the inverters side-by-side horizontally with no space, remove the top cover of the inverter before use (refer
to [2. 2] of instruction manual (E6582062)). When using the inverter in locations with temperatures above 50°C, use
the inverter with the operation panel removed and use the inverter with the output current reduced (refer to
"Instruction manual for load reduction").
The space shown in the figure above is the minimum allowable space. Because the inverter has cooling fans built in
on the top or bottom surfaces, make the space on top and bottom as large as possible to allow for air passage.
• Do not install in any location with high humidity or high temperatures and where there are large amounts
of dust, metallic fragments and oil mist.
Important
Memo
• We also provide models with IP55 protective construction for adverse environments.
11 cm
or more
H1(cm)
4
H 3 or more
H 3 or more
H2(cm)
10
10
25
25
15
15
20
15
E6582116
H3(cm)
10
25
25
25